| Plan Review Notes For Permit 22061577 |
| Permit Number |
22061577 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2022-07-08 14:22:05 | 1) PROVIDE MECHANICAL EQUIPMENT SIZING CALCULATIONS FOR | | | THE NEW HP-3. FEC C403.2.1 | | | | | | 2) PROVIDE THE OUTDOOR AIR CALCULATIONS FOR THIS TENANT | | | SPACE. FMC 403.3.1.1 AND TABLE 403.3.1.1 | | | | | | 3) PROVIDE THE SPECS FOR THE MECHANICAL SYSTEMS.FBC | | | 107.2.1 | | | | | | | | | MICHAEL EDWARDS | | | MECHANICAL EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL. 33401 | | | 561-805-6728 | | | [email protected] | | | |
|