2022-08-02 11:19:31CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2020 7TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1
 WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL
 MANUAL REVISED 2017
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020
 7TH EDITION
 FBC ACC = FLORIDA ACCESSIBILITY CODE 2020 7TH EDITION
 FBC EX = FLORIDA EXISTING BUILDING CODE 2020 7TH
 EDITION
 FBC PL = FLORIDA PLUMBING CODE 2020 7TH EDITION
 FBC FG = FLORIDA FUEL GAS CODE 2020 7TH EDITION
 FAC= FLORIDA ADMINISTRATIVE CODE
 FS = FLORIDA STATUTES
  
 22061550 2414 FLORIDA AVE
  
 1ST REVIEW
 PLUMBING COMMENTS: DENIED
  
 1.THE BACKFLOW PERMIT(S) ARE REQUIRED TO BE SUBMITTED
 PRIOR TO ISSUANCE OF THE PRIMARY PERMIT (AS
 APPLICABLE). YOU CAN SUBMIT AN APPLICATION "TBD" (TO BE
 DETERMINED) IF YOU DO NOT HAVE A CONTRACTOR SELECTED BY
 EMAILING A COMPLETED PERMIT APPLICATION TO
 [email protected] . YOU WILL RECEIVE INSTRUCTIONS
 TO PAY FEES AND UPLOAD PLANS. YOU MAY UPLOAD PLANS AND
 PAY FEES AT A FUTURE DATE, BUT THE APPLICATION IS
 REQUIRED AT THIS TIME. WE RECOMMEND THAT YOU PAY FEES
 AND UPLOAD PLANS AT THE SAME TIME. A SEPARATE PERMIT IS
 REQUIRED HOWEVER A REVIEW OF THE SYSTEM UNDER THE MAIN
 PERMIT IS ALSO REQUIRED.
  
 2. A-700/DETAILS 1 & 2:CLEARANCE AROUND A WATER CLOSET
 SHALL BE 60 INCHES MINIMUM MEASURED PERPENDICULAR FROM
 THE SIDE WALL AND 56 INCHES DEEP MINIMUM FOR WALL HUNG
 WATER CLOSETS AND 59 INCHES DEEP MINIMUM FOR FLOOR
 MOUNTED WATER CLOSETS MEASURED PERPENDICULAR TO THE
 REAR WALL PER FBC ACC 604.3.1 AND 604.8.1.1.
 SEE P-103 PLUMBING FIXTURE SCHEDULE. SPECIFIED A.S.
 3043.001 MADERA WATER CLOSET IS FLOOR MOUNTED AND
 REQUIRES 59 INCHES DEEP MINIMUM CLEAR FLOOR SPACE FOR
 FLOOR MOUNTED WATER CLOSETS MEASURED PERPENDICULAR TO
 THE REAR WALL,
  
 3.THE SIDE WALL GRAB BAR SHALL BE 42 INCHES LONG
 MINIMUM, LOCATED 12 INCHES (305 MM) MAXIMUM FROM THE
 REAR WALL AND EXTENDING 54 INCHES MINIMUM FROM THE REAR
 WALL PER FBC ACC 604.5.1
  
 4.THE REAR WALL GRAB BAR SHALL BE 36 INCHES LONG
 MINIMUM AND EXTEND FROM THE CENTERLINE OF THE WATER
 CLOSET 12 INCHES MINIMUM ON ONE SIDE AND 24 INCHES
 MINIMUM ON THE OTHER SIDE PER FBC ACC 604.5.2
  
 5.PER FBC ACC 609.4, GRAB BARS SHALL BE INSTALLED IN A
 HORIZONTAL POSITION, 33 INCHES MINIMUM AND 36 INCHES
 MAXIMUM ABOVE THE FINISH FLOOR MEASURED TO THE TOP (NOT
 THE CENTER) OF THE GRIPPING SURFACE,
  
 6. RE: MEZZANINE SINK: PLEASE NOTE WHERE SINKS ARE
 PROVIDED, AT LEAST 5 PERCENT, BUT NO FEWER THAN ONE, OF
 EACH TYPE PROVIDED IN EACH ACCESSIBLE ROOM OR SPACE
 SHALL COMPLY WITH FBC ACC 606 PER FBC ACC 212.3.
 LAVATORIES AND SINKS SHALL BE INSTALLED WITH THE FRONT
 OF THE HIGHER OF THE RIM OR COUNTER SURFACE 34 INCHES
 MAXIMUM ABOVE THE FINISH FLOOR OR GROUND PER FBC ACC
 606.3. PER WPB FBC 107.2.1, SHOW COMPLIANCE.
 FBC ACC ADVISORY 202.3 ALTERATIONS. ALTHOUGH COVERED
 ENTITIES ARE PERMITTED TO LIMIT THE SCOPE OF AN
 ALTERATION TO INDIVIDUAL ELEMENTS, THE ALTERATION OF
 MULTIPLE ELEMENTS WITHIN A ROOM OR SPACE MAY PROVIDE A
 COST-EFFECTIVE OPPORTUNITY TO MAKE THE ENTIRE ROOM OR
 SPACE ACCESSIBLE. ANY ELEMENTS OR SPACES OF THE
 BUILDING OR FACILITY THAT ARE REQUIRED TO COMPLY WITH
 THESE REQUIREMENTS MUST BE MADE ACCESSIBLE WITHIN THE
 SCOPE OF THE ALTERATION, TO THE MAXIMUM EXTENT
 FEASIBLE. IF PROVIDING ACCESSIBILITY IN COMPLIANCE WITH
 THESE REQUIREMENTS FOR PEOPLE WITH ONE TYPE OF
 DISABILITY (E.G., PEOPLE WHO USE WHEELCHAIRS) IS NOT
 FEASIBLE, ACCESSIBILITY MUST STILL BE PROVIDED IN
 COMPLIANCE WITH THE REQUIREMENTS FOR PEOPLE WITH OTHER
 TYPES OF DISABILITIES (E.G., PEOPLE WHO HAVE HEARING
 IMPAIRMENTS OR WHO HAVE VISION IMPAIRMENTS) TO THE
 EXTENT THAT SUCH ACCESSIBILITY IS FEASIBLE.
 FLORIDA REQUIREMENTS FOR EXISTING PARKING
 S.553.5041(G), F.S., AND VERTICAL ACCESSIBILITY
 S.553.509, F.S., ARE INCORPORATED INTO THIS GENERAL
 SECTION APPLICABLE TO ALTERATIONS. FLORIDA REQUIREMENTS
 MAY BE WAIVED DOWN TO THE ADA STANDARDS REQUIREMENTS.
  
  
 7. BUILDING OCCUPANCY IS CLASSIFIED BUSINESS. PER FBC
 PL 403.1, 403.5, 410.3 AND FBC ACC 211.3, PROVIDE TWO
 DRINKING FOUNTAINS. ONE DRINKING FOUNTAIN SHALL COMPLY
 WITH 602.1 THROUGH 602.6 AND ONE DRINKING FOUNTAIN
 SHALL COMPLY WITH 602.7. WHERE A SINGLE DRINKING
 FOUNTAIN COMPLIES WITH 602.1 THROUGH 602.6 AND 602.7,
 IT SHALL BE PERMITTED TO BE SUBSTITUTED FOR TWO
 SEPARATE DRINKING FOUNTAINS.
 DRINKING FOUNTAINS SHALL BE LOCATED ON AN ACCESSIBLE
 ROUTE WITHIN 500 FEET OF ALL TENANTS.
  
 8.MANUFACTURER'S SPECIFICATION/INSTALLATION MANUAL FOR
 THE FOLLOWING SHALL BE PROVIDED FOR THE FOLLOWING:
 ***A) WATER HEATER- CHRONOMITE CMI SERIES W/INTEGRAL
 ASSE 1070 TEMPERATURE LIMITING DEVICE AS NOTED ON P-104
 WATER RISERS AND LISTED BELOW:
 CMI-20L/120
 CMI-15L/208
 CMI-30L/208
 ***B) BACKFLOW PREVENTER DEVICES
  
 9. WATER HEATERS SERVING TENANT TOILET ROOM LAVATORIES
 ARE PROVIDED WITH INTEGRAL ASSE 1070 TEMPERATURE
 LIMITING DEVICES (P-104); PLUMBING FIXTURE SCHEDULE
 P-2-LAVATORY CALLS SENSOR FAUCET WITH A 605XTMV1070
 THERMOSTATIC MIXING VALVE. PER WPB FBC 107.2.1, PLEASE
 CLARIFY.
  
 10.P-104: 1 INCH COLD WATER FEED TO INDIVIDUAL TOILET
 ROOMS AT 28 GPM EXCEEDS RECOMMENDED VELOCITY CALLED OUT
 IN FBC PL APPENDIX E/ FIGURE E103.3(3).
  
 11. P-101/P-103: MEZZANINE SANITARY SHALL CONNECT
 DOWNSTREAM OF THE MOST DOWNSTREAM WATER CLOSET IN
 TENANT SPACE 6 PER FBC PL 909.1 AND 912.1.
  
 12.PER WPB FBC 107.2.1, PROVIDE A DETAIL FOR THE SINK
 (P-3) AND DISHWASHER CONNECTION IN TENANT SPACE 6;
 ***A) THE WASTE CONNECTION OF A RESIDENTIAL DISHWASHER
 SHALL CONNECT DIRECTLY TO A WYE BRANCH FITTING ON THE
 TAILPIECE OF THE KITCHEN SINK, DIRECTLY TO THE
 DISHWASHER CONNECTION OF A FOOD WASTE DISPOSER, OR
 THROUGH AN AIR BREAK TO A STANDPIPE. THE WASTE LINE OF
 A RESIDENTIAL DISHWASHER SHALL RISE AND BE SECURELY
 FASTENED TO THE UNDERSIDE OF THE SINK RIM OR COUNTER
 TOP. FBC PL 409.4
 ***B) COMPONENTS (SINK, WATER HEATER, TMV) AND SHUT-OFF
 VALVES OF THE COLD, HOT AND TEMPERED WATER.
  
 13.PER WPB FBC 107.2.1, PROVIDE A DETAIL FOR LAVATORIES
 (P-2) IN TENANT SPACE 6 TO INCLUDE LAVATORIES, WATER
 HEATER, TMV AND SHUT-OFF VALVES OF THE COLD, HOT AND
 TEMPERED WATER.
  
 14.PER WPB FBC 107.2.1, PROVIDE A DETAIL FOR LAVATORY
 (P-2) IN TYPICAL SINGLE TOILET ROOM TO INCLUDE
 LAVATORY, WATER HEATER, TMV AND SHUT-OFF VALVES OF THE
 COLD, HOT AND TEMPERED WATER
  
 15.ALL COMPONENTS IN THE DOMESTIC WATER SYSTEM SHALL BE
 LEAD FREE IN ACCORDANCE WITH FBC PL 605.2 AND 605.2.1.
 PER WPB FBC 107.2.1, PROVIDE NOTE ON PLANS STATING THE
 SAME.
  
 16.PER WPB FBC 107.2.1, PROVIDE PIPE HANGER DETAIL WITH
 A NOTE STATING, "HORIZONTAL PIPE SHALL BE SUPPORTED IN
 ACCORDANCE WITH FBC PL TABLE 308.5."
  
 17.PROVIDE ENERGY EFFICIENCY FOR WATER HEATER(S);
 COMPLY WITH FBC EC TABLE C404.2
  
 18.PER WPB FBC 107.2.1, PROVIDE A SLAB REPAIR DETAIL ON
 THE PLANS. SHOW THE WIDTH OF THE REPAIR, THE MINIMUM
 THICKNESS AND PSI OF THE CONCRETE TO BE REPLACED. SHOW
 SIZE, LENGTH, SPACING (ON CENTER), MINIMUM EMBEDMENT
 AND ANCHORING/ADHESIVE MATERIAL FOR DOWELS. THE REPAIR
 SHALL ALSO INCLUDE TERMITE TREATMENT OF THE SOIL AS
 WELL AS THE REQUIRED VAPOR BARRIER OVER WELL COMPACTED
 SOIL. A COPY OF THE TERMITE CERTIFICATE SHALL BE ONSITE
 FOR FINAL INSPECTION.
  
 19.PER WPB FBC 107.2.1, TO SHOW COMPLIANCE WITH FBC PL
 704.1, PROVIDE NOTE STATING "HORIZONTAL DRAINAGE PIPING
 LESS THAN 3 INCH DIAMETER SHALL HAVE A MINIMUM SLOPE OF
 1/4 INCH PER FOOT. 3 INCH TO 6 INCH DIAMETER SHALL HAVE
 A MINIMUM SLOPE OF 1/8 INCH PER FOOT".
  
 20.A VACUUM BREAKER IS REQUIRED ON ALL HOSE BIBS.
 PROVIDE A SPEC AND DETAIL.
  
 21.PER FBC PL 708.1.4, PROVIDE A CLEANOUT AT THE 90
 DEGREE CHANGES OF DIRECTION IN THE BUILDING DRAINS FOR
 BAYS 1, 2, 3, 4 AND 5.
  
 22.PER WPB FBC 107.2.1, PROVIDE DETAILS FOR THE
 FOLLOWING:
 ***A) EXTERIOR CLEANOUT AT JUNCTION OF THE BUILDING
 DRAIN AND BUILDING SEWER
 ***B) INTERIOR FLOOR CLEANOUT
 ***C) INTERIOR WALL CLEANOUT
  
  
 END OF COMMENTS.
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS. ALL PLANS TO BE SIGNED
 AND SEALED BY THE DESIGNER AS REQUIRED BY FAC AND FS.
  
  
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER PX928
 PLUMBING INSPECTOR BN2148
 CITY OF WEST PALM BEACH
 EMAIL [email protected]
 MOBILE 561-246-0882
 PLEASE NOTE THAT I TYPICALLY WORK ON TUESDAYS AND
 THURSDAYS
  