Plan Review Notes
Plan Review Notes For Permit 22061550
Permit Number 22061550
Review Stop M
Sequence Number 1
Notes
Date Text
2022-07-27 16:19:14 
 PROVIDE A DEMO DRAWING FOR THE REMOVING OF EXISTING
 WORK. FBC 107.2.1
 PROVIDE EQUIPMENT SIZING CALCULATIONS FOR EACH UNIT.
 FMC C403.2.1
 PROVIDE THE OUTDOOR AIR CALCULATIONS BASED ON THE
 OCCUPANCY CLASSIFICATION THAT MOST CLOSELY RESEMBLES
 THE USE OF EACH SPACE. IT APPEARS THAT OCCUPANCY WOULD
 BE MUSEUM/GALLERIES. PROVIDE A USE OF SPACE LETTER SO
 WE CAN DETERMINE THE BEST OCCUPANCY CLASSIFICATION TO
 USE FROM FMC TABLE 403.3.1.1.
 SHEET M-101 HAS A NOTE THAT STATES; SEE MEZZANINE PLAN
 FOR CONTINUATION. PROVIDE THIS DRAWING AS IT IS NOT IN
 THIS SUBMITTAL. FBC 107.2.1
  
  