| Plan Review Notes For Permit 22061548 |
| Permit Number |
22061548 |
|
| Review Stop |
B |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2022-08-12 17:46:38 | RESIDENTIAL (R2) BUILDING REVIEW COMMENTS | | | CODE: FBC 7TH EDITION (2020) AND CITY AMENDMENTS. | | | PERMIT #22061548 | | | | | | 1- THE FLAME SPREAD TEST REPORT SUBMITTED IS FOR | | | PROFLEX LV-200 UNDERLAYMENT. THE SOUND TRANSMISSION | | | CLASS (STC) TEST REPORT AND THE IMPACT INSULATION CLASS | | | (IIC) TEST REPORT SUBMITTED IS FOR PROTECT WRAP | | | WHISPERMAT LVT. | | | THE FLAME SPREAD TEST REPORT FOR THE FLOORING | | | UNDERLAYMENT AND THE SOUND TRANSMISSION TEST REPORT | | | SUBMITTED ARE FOR TWO DIFFERENT MANUFACTURERS. THE | | | FLAME SPREAD REPORT AND THE SOUND TEST REPORT NEED TO | | | BE DONE FOR THE SAME UNDERLAYMENT MATERIAL AND | | | MANUFACTURER. PLEASE RESUBMIT. | | | | | | PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY | | | QUESTIONS REGARDING THESE COMMENTS, | | | JULIO GOMEZ | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | DEVELOPMENT SERVICES DEPARTMENT | | | BUILDING DIVISION | | | (561)805-6712 | | | [email protected] |
|