| 2022-06-30 13:16:52 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE |
| | MARSHAL, WITH THE FOLLOWING COMMENTS: |
| | |
| | 1) THERE IS AN INDICATION OF THE INSTALL OF WOOD |
| | FLOORING IN THE MASTER BEDROOM, BUT NO SPEC SHEET NOR A |
| | PRODUCT NAME FOR THE ACTUAL PROPOSED FLOORING. |
| | |
| | WOOD FLOORING IS MANUFACTURED AROUND THE WORLD AND NOT |
| | ALL ARE TESTED AND MEETING LISTED AND NFPA STANDARDS. |
| | |
| | PER NFPA 101, CH 30 |
| | |
| | 30.3.3.3 INTERIOR FLOOR FINISH. |
| | 30.3.3.1 GENERAL. INTERIOR FINISH SHALL BE IN |
| | ACCORDANCE WITH |
| | SECTION 10.2. |
| | |
| | 10.2.7.2* FLOOR COVERINGS, OTHER THAN CARPET FOR WHICH |
| | 10.2.2.2 |
| | ESTABLISHES REQUIREMENTS FOR FIRE PERFORMANCE, SHALL |
| | HAVE A |
| | MINIMUM CRITICAL RADIANT FLUX OF 0.1 W/CM2. |
| | |
| | FOR THE OFFICIAL RECORD, PLEASE PROVIDE THE WOOD |
| | FLOORING NAME AND THE PRODUCT SPEC SHEETS OF THE |
| | PROPOSED |
| | WOOD FLOORING INDICATING THE FIRE BEHAVIOR RATING. |
| | |
| | |
| | 2) THERE IS AN INDICATION OF WALL TILE WORK IN THE |
| | MASTER BATHROOM THAT MY INVOLVE A FIRE RATED WALL. |
| | |
| | ENSURE FIRE RATED TENANT SEPARATION/CORRIDOR WALLS ARE |
| | REPAIRED TO THE EXISTING FIRE RATED SEPARATION. |
| | |
| | PROVIDE AN APPLICABLE NOTE OF ACKNOWLEDGMENT. |
| | |
| | |
| | |
| | |
| | 3) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET |
| | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE |
| | ABOVE. |
| | |
| | |
| | 4) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE |
| | RE-SUBMITTAL OF THE ABOVE. |
| | |
| | |
| | PETER LEDUC |
| | FIRE MARSHAL |
| | 561-804-4709 |