| Date |
Text |
| 2022-10-12 07:44:09 | 3RD REVIEW FMC |
| | PERMIT: 22061540 |
| | |
| | CODES IN EFFECT: 2020 |
| | |
| | FBC- FLORIDA BUILDING CODE |
| | FMC- FLORIDA MECHANICAL CODE |
| | FEC- FLORIDA ENERGY CONSERVATION |
| | FGC- FLORIDA FUEL GAS |
| | FEX- FLORIDA EXISTING BUILDING CODE |
| | FRC- FLORIDA RESIDENTIAL BUILDING CODE |
| | F.S.- FLORIDA STATUTES |
| | FAC- FLORIDA ACCESSIBILITY CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | IN 2007 THIS 2 STORY GARAGE WITH A REC. ROOM ABOVE WAS |
| | BUILT. WE DO NOT HAVE ANY RECORDS OF THIS GARAGE BEING |
| | CONVERTING TO A POOL HOUSE. IN 2017 THE POOL WAS |
| | CONSTRUCTED AT THE REAR OF THE HOME. ACCORDING TO THE |
| | PICTURES THAT WERE SUBMITTED IN THIS REVIEW CYCLE THE |
| | GARAGE DOORS HAVE BEEN REMOVED AND SLIDING GLASS DOORS |
| | WERE ADDED. TO RESOLVE THIS ISSUE A DESIGNER MUST SHOW |
| | THAT THE CONVERSION INCLUDING THE DOORS WILL MEET THE |
| | CODE FOR WIND LOAD AND STRUCTURE. IF ANY ELECTRICAL OR |
| | PLUMBING WAS COMPLETED THEN THEY TOO MUST MEET THE |
| | CODES. A BUILDING PERMIT IS REQUIRED WITH THIS CHANGE |
| | OF USE. THE ORIGINAL GARAGE WAS CONVERTED TO HABITABLE |
| | SPACE WITHOUT PERMITS. THE ENERGY CALCULATIONS MUST |
| | SHOW THESE SLIDING GLASS DOORS IN THE CALCULATIONS AND |
| | THE MANUAL J MUST REFLECT THE SLIDING DOORS AS WELL. I |
| | CANNOT APPROVE THE MECHANICAL ON THIS STRUCTURE UNTIL |
| | THE STRUCTURE IS PERMITTED FOR THE NEW USE. |
| | |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM. |
| | |
| | MICHAEL EDWARDS |
| | MECHANICAL EXAMINER |
| | 401 CLEMATIS STREET |
| | WEST PALM BEACH FL. 33401 |
| | 561-805-6728 |
| | [email protected] |
| | |