| 2022-09-30 07:47:28 | 2ND CYCLE REVIEW: |
| | PLEASE SEE 1ST CYCLE COMMENTS BELOW. IT ISN'T CLEAR |
| | WHAT WAS DONE WITH THE GARAGE DOOR BUT THE ENERGY |
| | CALCULATIONS SUBMITTED ON 9/26/2022 DOES NOT SHOW ANY |
| | DOORS IN THE CALCULATIONS. IF THIS ORIGINAL GARAGE WAS |
| | CONVERTED THEN YOU MUST APPLY FOR A BUILDING PERMIT |
| | WITH A CHANGE OF USE AND PROVIDE DRAWINGS FOR THIS. |
| | THE DIGITAL SIGNATURE OF KAREN OLIVER HAS BEEN ALTERED |
| | AND IS NO LONG A VALID DIGITAL SIGNATURE. PLEASE SUBMIT |
| | AN UNALTERED DRAWING WITH HER DIGITAL SIGNATURE. |
| | |
| | 1ST REVIEW FMC |
| | PERMIT: 22061540 |
| | |
| | CODES IN EFFECT: 2020 |
| | |
| | FBC- FLORIDA BUILDING CODE |
| | FMC- FLORIDA MECHANICAL CODE |
| | FEC- FLORIDA ENERGY CONSERVATION |
| | FGC- FLORIDA FUEL GAS |
| | FEX- FLORIDA EXISTING BUILDING CODE |
| | FRC- FLORIDA RESIDENTIAL BUILDING CODE |
| | F.S.- FLORIDA STATUTES |
| | FAC- FLORIDA ACCESSIBILITY CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | OUR RECORDS INDICATE THAT THIS BUILDING WAS BUILT AS A |
| | 2 STORY BUILDING WITH A 2 CAR GARAGE WITH A CONDITIONED |
| | RECREATION ROOM ABOVE. IF THE USE OF THE GARAGE IS |
| | GOING TO BE CHANGED TO LIVING SPACE A CHANGE OF USE |
| | WILL NEED TO BE SUBMITTED WITH A PERMIT AND DRAWINGS |
| | SHOWING ALL WORK. IF THE MECHANICAL SYSTEM PROPOSED IS |
| | FOR DEHUMIDIFICATION ONLY THEN PROVIDE DEHUMIDIFICATION |
| | SYSTEMS AND PLANS SHOWING THIS. IF THE SPACE IS TO BE |
| | CONDITIONED WITH AC AND OR HEAT THEN THE CHANGE OF USE |
| | WITH DOCUMENTS WILL BE REQUIRED. FBC 107.2.1 |
| | |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM. |
| | |
| | MICHAEL EDWARDS |
| | MECHANICAL EXAMINER |
| | 401 CLEMATIS STREET |
| | WEST PALM BEACH FL. 33401 |
| | 561-805-6728 |
| | [email protected] |
| | |