| Plan Review Notes For Permit 22061488 |
| Permit Number |
22061488 |
|
| Review Stop |
M |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2023-04-24 16:44:28 | 3RD REVIEW FMC | | | PERMIT: 22061488 | | | | | | CODES IN EFFECT: 2020 | | | | | | FBC- FLORIDA BUILDING CODE | | | FMC- FLORIDA MECHANICAL CODE | | | FEC- FLORIDA ENERGY CONSERVATION | | | FGC- FLORIDA FUEL GAS | | | FEX- FLORIDA EXISTING BUILDING CODE | | | FRC- FLORIDA RESIDENTIAL BUILDING CODE | | | F.S.- FLORIDA STATUTES | | | FAC- FLORIDA ACCESSIBILITY CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) THE LATEST MECHANICAL DRAWING SUBMITTED IS FOR WHAT | | | APPEARS TO BE A MUCH LARGER STRUCTURE. THE PROPOSED | | | MECHANICAL LAYOUT SHOWS A BATHROOM AND WALK IN CLOSET | | | THAT APPEARS TO BE AN ADDITION TO AN EXISTING | | | STRUCTURE. PROVIDE THE ENERGY CALCULATIONS FOR THIS | | | ADDITION. PROVIDE THE MECHANICAL EQUIPMENT SIZING | | | CALCULATIONS FOR THE ENTIRE STRUCTURE. THE BATH EXHAUST | | | FANS MUST BE A MINIMUM OF 50 CFM???S INTERMITTENT OR 20 | | | CFM CONTINUOUS. SHOW ALL THE BATH FANS AND EXHAUST | | | TERMINATIONS. FBC 107.3.5 | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM. | | | | | | MICHAEL EDWARDS | | | MECHANICAL EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL. 33401 | | | 561-805-6728 | | | [email protected] | | | |
|