2023-02-28 07:58:28PLEASE SUBMIT THE DOCUMENTS REQUESTED IN THE 1ST CYCLE
 MECHANICAL REVIEW. THE ENERGY CALCULATIONS WERE NOT
 SUBMITTED AND THE EOR DID NOT DIGITALLY SIGN THE
 DOCUMENTS.
  
 1) OUR RECORDS INDICATE THERE HAS NEVER BEEN A
 PERMITTED MECHANICAL SYSTEM AT THIS STRUCTURE. PLEASE
 PROVIDE THE MECHANICAL EQUIPMENT SIZING CALCULATIONS
 FOR THIS PROJECT. FEC C403.2.1
  
 2) EOR THAT IS NAME ON EACH DRAWING MUST DIGITALLY SIGN
 EACH DRAWING. FS 471/481
  