2022-07-22 11:35:45FIRE PROVISO:
  
 PROVIDE 80 BC RATED PORTABLE FIRE EXTINGUISHER WITHIN
 100 FEET OF THE DISPENSERS. NFPA 30A 9.2.5.2
  
 DETAILED WARNING SIGNAGE SHALL BE CONSPICUOUSLY POSTED
 PER NFPA 30A 9.2.5.4
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709