| Plan Review Notes For Permit 22061484 |
| Permit Number |
22061484 |
|
| Review Stop |
Z |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2022-07-25 12:37:25 | 07/25/22 FAILED | | | | | | PER CITY CODE, MECHANICAL EQUIPMENT MUST NOT ENCROACH | | | MORE THAN 4 FT IN TO ANY SETBACK. BASED ON THE SURVEY, | | | TTHE GENERATOR ENCROACHES 4.5 FT INTO THE 8.5 FT | | | SETBACK. | | | | | | ALEXANDER FOWLKES | | | 5618221431 | | | [email protected] |
|