| Plan Review Notes For Permit 22061424 |
| Permit Number |
22061424 |
|
| Review Stop |
G |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2023-04-26 07:15:59 | 2ND GAS REVIEW | | | | | | THIS PLAN WAS REVIEWED FOR CODE COMPLIANCE AND FAILED | | | BY RYAN BROWN WITH THE FOLLOWING COMMENTS. | | | | | | 1. DONE | | | A) DONE | | | B) DONE | | | C) DONE | | | D) IF THE SCALE AND THE FLOOR PLAN IS CORRECT SEE | | | COMMENT #2 | | | INCLUDE THE SIZE OF THE ROOM THE RANGE IS BEING | | | INSTALLED IN ORDER TO ADDRESS COMMENT #2. | | | | | | 2. IN DOING THE CALCULATIONS FOR A 268K BTU RANGE, NOT | | | ENOUGH SPACE IS PROVIDED FOR COMUBSTION AIR. ASSUMING | | | THE SCALE IS CORRECT, COMBUSTION AIR MUST BE PROVIDED | | | FOR THE RANGE IN THE SPACE INSTALLED. THE REQUIRED | | | COMBUSTION AIR MUST BE DETAILED IN THIS PLAN IN ORDER | | | TO PASS REVIEW. | | | 2020 FRC G2407.1 - PLEASE SHOW THE REQUIRED COMBUSTION | | | AIR CALCULATIONS FOR THE RANGE. | | | | | | 3. DONE | | | | | | 4. DONE | | | | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM. | | | | | | | | | RYAN W. BROWN | | | CHIEF PLUMBING INSPECTOR | | | OFFICE: 561-805-6692 | | | CELL: 561-517-4293 | | | EMAIL: [email protected] | | | | | | | | | V7 FPC - 2020 FLORIDA PLUMBING CODE | | | V7 FGC - 2020 FLORIDA FUEL GAS | | | V7 FRC - 2020 FLORIDA RESIDENTIAL BUILDING CODE | | | V7 FAC - 2020 FLORIDA ACCESSIBILITY CODE | | | V7 FEX - 2020 FLORIDA EXISTING BUILDING CODE | | | V7 FEC - 2020 FLORIDA ENERGY CONSERVATION | | | 2021 F.S. - 2021 FLORIDA STATUTES | | | 2021 F.A.C. - 2021 FLORIDA ADMINISTRATIVE CODE | | | 2017 WPB AMEND - 2017 WEST PALM BEACH AMENDMENTS TO THE | | | FBC CHAPTER 1 | | | |
|