| 2023-04-21 07:49:03 | 1ST GAS REVIEW |
| | |
| | THIS PLAN WAS REVIEWED FOR CODE COMPLIANCE AND FAILED |
| | BY RYAN BROWN WITH THE FOLLOWING COMMENTS. |
| | |
| | 1. 2017 WPB AMENDS 107.2.1 - INCLUDE A FLOOR PLAN THAT |
| | SHOWS: |
| | A) THE ROUTING OF THE GAS LINE IN REFERENCE TO THE |
| | HOUSE |
| | B) THE LOCATION OF THE APPLIANCES |
| | C) THE LOCATION OF THE SLEEVE AND TYPE OF FLOOR IT IS |
| | SLEEVING UNDER (SLAB HOME OR STEM WALL) |
| | D) INCLUDE THE SIZE OF THE ROOM THE RANGE IS BEING |
| | INSTALLED IN ORDER TO ADDRESS COMMENT #2. |
| | |
| | 2. 2020 FRC G2407.1 - PLEASE SHOW THE REQUIRED |
| | COMBUSTION AIR CALCULATIONS FOR THE RANGE. |
| | |
| | 3. 2017 WPB AMENDS 107.2.1 - ONE DRAWING SHOWS PE UNDER |
| | THE HOUSE (WHICH IS NOT ALLOWED PER G2415.17.1) AND THE |
| | OTHER CSST. PLEASE CLARIFY AND SHOW ON BOTH, THE RISER |
| | AND THE FLOOR PLAN DRAWINGS. |
| | |
| | 4. 2017 WPB AMENDS 107.2.1 - PLEASE HAVE THE PERSON WHO |
| | DESIGNED THE DRAWING PRINT THEIR NAME, SIGN THEIR NAME, |
| | AS WELL AS PUT THE CONTRACTOR'S NUMBER ON THE DRAWING |
| | AS REQUIRED BY THE WEST PALM BEACH AMENDMENTS TO |
| | CHAPTER 1. |
| | |
| | |
| | |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM. |
| | |
| | |
| | RYAN W. BROWN |
| | CHIEF PLUMBING INSPECTOR |
| | OFFICE: 561-805-6692 |
| | CELL: 561-517-4293 |
| | EMAIL: [email protected] |
| | |
| | |
| | V7 FPC - 2020 FLORIDA PLUMBING CODE |
| | V7 FGC - 2020 FLORIDA FUEL GAS |
| | V7 FRC - 2020 FLORIDA RESIDENTIAL BUILDING CODE |
| | V7 FAC - 2020 FLORIDA ACCESSIBILITY CODE |
| | V7 FEX - 2020 FLORIDA EXISTING BUILDING CODE |
| | V7 FEC - 2020 FLORIDA ENERGY CONSERVATION |
| | 2021 F.S. - 2021 FLORIDA STATUTES |
| | 2021 F.A.C. - 2021 FLORIDA ADMINISTRATIVE CODE |
| | 2017 WPB AMEND - 2017 WEST PALM BEACH AMENDMENTS TO THE |
| | FBC CHAPTER 1 |
| | |