Plan Review Notes
Plan Review Notes For Permit 22061424
Permit Number 22061424
Review Stop G
Sequence Number 1
Notes
Date Text
2023-04-21 07:49:031ST GAS REVIEW
  
 THIS PLAN WAS REVIEWED FOR CODE COMPLIANCE AND FAILED
 BY RYAN BROWN WITH THE FOLLOWING COMMENTS.
  
 1. 2017 WPB AMENDS 107.2.1 - INCLUDE A FLOOR PLAN THAT
 SHOWS:
 A) THE ROUTING OF THE GAS LINE IN REFERENCE TO THE
 HOUSE
 B) THE LOCATION OF THE APPLIANCES
 C) THE LOCATION OF THE SLEEVE AND TYPE OF FLOOR IT IS
 SLEEVING UNDER (SLAB HOME OR STEM WALL)
 D) INCLUDE THE SIZE OF THE ROOM THE RANGE IS BEING
 INSTALLED IN ORDER TO ADDRESS COMMENT #2.
  
 2. 2020 FRC G2407.1 - PLEASE SHOW THE REQUIRED
 COMBUSTION AIR CALCULATIONS FOR THE RANGE.
  
 3. 2017 WPB AMENDS 107.2.1 - ONE DRAWING SHOWS PE UNDER
 THE HOUSE (WHICH IS NOT ALLOWED PER G2415.17.1) AND THE
 OTHER CSST. PLEASE CLARIFY AND SHOW ON BOTH, THE RISER
 AND THE FLOOR PLAN DRAWINGS.
  
 4. 2017 WPB AMENDS 107.2.1 - PLEASE HAVE THE PERSON WHO
 DESIGNED THE DRAWING PRINT THEIR NAME, SIGN THEIR NAME,
 AS WELL AS PUT THE CONTRACTOR'S NUMBER ON THE DRAWING
 AS REQUIRED BY THE WEST PALM BEACH AMENDMENTS TO
 CHAPTER 1.
  
  
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
  
 RYAN W. BROWN
 CHIEF PLUMBING INSPECTOR
 OFFICE: 561-805-6692
 CELL: 561-517-4293
 EMAIL: [email protected]
  
  
 V7 FPC - 2020 FLORIDA PLUMBING CODE
 V7 FGC - 2020 FLORIDA FUEL GAS
 V7 FRC - 2020 FLORIDA RESIDENTIAL BUILDING CODE
 V7 FAC - 2020 FLORIDA ACCESSIBILITY CODE
 V7 FEX - 2020 FLORIDA EXISTING BUILDING CODE
 V7 FEC - 2020 FLORIDA ENERGY CONSERVATION
 2021 F.S. - 2021 FLORIDA STATUTES
 2021 F.A.C. - 2021 FLORIDA ADMINISTRATIVE CODE
 2017 WPB AMEND - 2017 WEST PALM BEACH AMENDMENTS TO THE
 FBC CHAPTER 1
  