| 2022-08-17 08:52:35 | 1ST REVIEW FBC-2020 PLUMBING |
| | PERMIT- 22061421 |
| | 8/17/2022 |
| | |
| | CODES IN EFFECT: |
| | FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020 |
| | FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION |
| | 2020 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) PLEASE PROVIDE SITE-SPECIFIC ENLARGED ACCESSIBLE |
| | TOILET ROOM DRAWINGS WITH THE FOLLOWING DETAILS PER FBC |
| | ACC: |
| | A) CLEAR FLOOR SPACE DIAGRAM AND DIMENSIONS FOR THE |
| | WATER CLOSETS- SECTION 604.3. |
| | B) CLEAR FLOOR SPACE DIAGRAM AND DIMENSIONS FOR THE |
| | LAVATORIES- SECTION 606.2. |
| | C) TURNING SPACE DIAMETERS- SECTION 304.3. |
| | D) CENTERLINES OF THE WATER CLOSETS FROM THE SIDE |
| | WALLS- SECTION 604.2. |
| | E) HEIGHTS OF THE WATER CLOSET SEATS FROM THE FINISHED |
| | FLOORS- SECTION 604.4. |
| | F) HEIGHTS OF THE LAVATORY SINK RIM OR COUNTER SURFACE |
| | FROM THE FINISHED FLOOR- SECTION 606.3. |
| | G) HEIGHTS OF THE MIRRORS FROM THE FINISHED FLOORS TO |
| | THE REFLECTIVE SURFACES- SECTION 603.3 |
| | H) LOCATIONS, LENGTHS, AND MOUNTING HEIGHTS OF GRAB |
| | BARS FOR THE WATER CLOSETS- SECTION 604.5 & 609.4, |
| | FIGURES 604. |
| | I) LOCATIONS OF THE WATER CLOSET FLUSH CONTROLS - |
| | SECTION 604.6. |
| | J) CENTERLINES OF THE TOILET PAPER DISPENSERS MEASURED |
| | FROM THE FRONTS OF THE WATER CLOSETS- SECTION AND |
| | FIGURE 604.7. |
| | K) KNEE AND TOE CLEARANCES FOR THE LAVATORIES- SECTION |
| | 606.2. |
| | |
| | 2) A0.02: SHOW THE CLEAR FLOOR SPACE DIAGRAMS |
| | (POSITIONED FOR FORWARD OR PARALLEL APPROACH) AT THE |
| | ACCESSIBLE SINKS IN THE EXAM ROOMS AND BREAKROOM- SEC. |
| | 606.2 FBC ACC. |
| | |
| | 3) A0.02: THE DRINKING FOUNTAINS APPEAR TO BE |
| | PROTRUDING INTO THE CIRCULATION PATH WHICH IS NOT |
| | ALLOWED PER SEC. 307.2 FBC ACC. |
| | |
| | 4) IF-501, 502, 503: THE BREAKROOM ELEVATION DETAIL |
| | DOES NOT SHOW THE REFRIGERATOR AND COFFEE MAKER, AND |
| | THEIR REACH RANGE COMPLIANCES- SEC. 308.1 FBC ACC. |
| | |
| | 5) P3.1: PROVIDE THE EFFICIENCY RATINGS OF THE WATER |
| | HEATERS- TABLE C404.2 FBC EC. |
| | |
| | 6) P3.1 EWH DETAIL: CORRECT THE 1/2-INCH THINK MINIMUM |
| | HW PIPE INSULATION THICKNESS TO SHOW 1-INCH MINIMUM- |
| | TABLE C403.2.10 FBC EC. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |