2022-08-17 15:21:401ST REVIEW FMC
 PERMIT: 22061421
  
 CODES IN EFFECT: 2020
  
 FBC- FLORIDA BUILDING CODE
 FMC- FLORIDA MECHANICAL CODE
 FEC- FLORIDA ENERGY CONSERVATION
 FGC- FLORIDA FUEL GAS
 FEX- FLORIDA EXISTING BUILDING CODE
 FRC- FLORIDA RESIDENTIAL BUILDING CODE
 F.S.- FLORIDA STATUTES
 FAC- FLORIDA ACCESSIBILITY CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) THE ADDRESS ON THE PERMIT APPLICATION AND THE
 DRAWINGS IS 575 FERN ST. WEST PALM BEACH BUT THE
 MECHANICAL EQUIPMENT SIZING CALCULATIONS HAVE AN
 ADDRESS OF 360 ROSEMARY. PLEASE PROVIDE THE CORRECT
 ADDRESS INCLUDING THE SUITE NUMBER. FBC 107.3.5
  
 2) PLEASE PROVIDE THE INTENDED USE OF THIS TENANT
 SPACE. IT APPEARS TO BE SOME TYPE OF MEDICAL OFFICE.
 FMC 407 AND FBC 469.
  
 3) THE LIFE SAFETY PLANS INDICATES RATED WALLS IN THIS
 TENANT SPACE. PLEASE SHOW THE FD IN ALL OF THE RATED
 WALL PENETRATIONS. FMC 607
  
 4) SHEET M-401 INDICATES THAT HP-D7 IS A 2-TON SYSTEM.
 THE EQUIPMENT SIZING CALCULATIONS SHOW THE MINIMUM FOR
 HP D7 IS 2.4 TONS. PLEASE EXPLAIN. FBC 107.3.5
  
 5) SHEET M-401 INDICATES THAT HP-D11 IS A 3-TON SYSTEM.
 THE EQUIPMENT SIZING CALCULATIONS SHOW THE MINIMUM FOR
 HP-D11 IS 1.9 TONS. PLEASE EXPLAIN THE 3-TON SYSTEM.
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  