| 2022-08-17 15:21:40 | 1ST REVIEW FMC |
| | PERMIT: 22061421 |
| | |
| | CODES IN EFFECT: 2020 |
| | |
| | FBC- FLORIDA BUILDING CODE |
| | FMC- FLORIDA MECHANICAL CODE |
| | FEC- FLORIDA ENERGY CONSERVATION |
| | FGC- FLORIDA FUEL GAS |
| | FEX- FLORIDA EXISTING BUILDING CODE |
| | FRC- FLORIDA RESIDENTIAL BUILDING CODE |
| | F.S.- FLORIDA STATUTES |
| | FAC- FLORIDA ACCESSIBILITY CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) THE ADDRESS ON THE PERMIT APPLICATION AND THE |
| | DRAWINGS IS 575 FERN ST. WEST PALM BEACH BUT THE |
| | MECHANICAL EQUIPMENT SIZING CALCULATIONS HAVE AN |
| | ADDRESS OF 360 ROSEMARY. PLEASE PROVIDE THE CORRECT |
| | ADDRESS INCLUDING THE SUITE NUMBER. FBC 107.3.5 |
| | |
| | 2) PLEASE PROVIDE THE INTENDED USE OF THIS TENANT |
| | SPACE. IT APPEARS TO BE SOME TYPE OF MEDICAL OFFICE. |
| | FMC 407 AND FBC 469. |
| | |
| | 3) THE LIFE SAFETY PLANS INDICATES RATED WALLS IN THIS |
| | TENANT SPACE. PLEASE SHOW THE FD IN ALL OF THE RATED |
| | WALL PENETRATIONS. FMC 607 |
| | |
| | 4) SHEET M-401 INDICATES THAT HP-D7 IS A 2-TON SYSTEM. |
| | THE EQUIPMENT SIZING CALCULATIONS SHOW THE MINIMUM FOR |
| | HP D7 IS 2.4 TONS. PLEASE EXPLAIN. FBC 107.3.5 |
| | |
| | 5) SHEET M-401 INDICATES THAT HP-D11 IS A 3-TON SYSTEM. |
| | THE EQUIPMENT SIZING CALCULATIONS SHOW THE MINIMUM FOR |
| | HP-D11 IS 1.9 TONS. PLEASE EXPLAIN THE 3-TON SYSTEM. |
| | |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM. |
| | |