| 2022-08-17 12:06:34 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE |
| | MARSHAL, WITH THE FOLLOWING COMMENTS: |
| | |
| | |
| | 1) SHEET AO.02 - THERE IS AN INDICATION OF AN EXIR DOOR |
| | FROM THE LAB ROOM HOWEVER, THERE IS NO CLEAR INDICATION |
| | THAT THIS EXIT LEADS TO A PUBLIC WAY. |
| | |
| | PER NFPA 101 CH 7 |
| | |
| | 7.7 DISCHARGE FROM EXITS |
| | 7.7.1* EXIT TERMINATION. EXITS SHALL TERMINATE |
| | DIRECTLY, AT A PUBLIC |
| | WAY OR AT AN EXTERIOR EXIT DISCHARGE, UNLESS OTHERWISE |
| | PROVIDED IN 7.7.1.2 |
| | THROUGH 7.7.1.4. |
| | |
| | PLEASE REVIEW AND PROVIDE DETAILS OF WHERE THIS EXIT |
| | LEADS MEETING THE REQIREMENTS OF A EXIT/PUBLIC WAY. |
| | |
| | |
| | 2) SHEET AO.15 - THERE ARE INDICATIONS WITHIN THE |
| | REMARKS SECTION OF THE DOOR SCHEDULE OR CARD READERS. |
| | |
| | CARD READER INSTALLATIONS SHALL BE UNDER SEPARATE |
| | PERMIT AND SHOP DRAWINGS AND COMPLY WITH NFPA 101 CH 7; |
| | 7.2.1.6 WHERE APPLICABLE. |
| | |
| | PLEASE PROVIDE A NOTE OF ACKNOWLEDGMENT ON THIS PLAN |
| | SHEET. |
| | |
| | |
| | 3) SHEET IF 200 - THERE IS AN INDICATION OF VWF, |
| | HOWEVER, THERE IS NO MANUFACTURE NAME NOR A PRODUCT |
| | SPECIFICATION SHEET MEETING THE REQUIRMENTS OF FLAME |
| | RATING. |
| | |
| | PER NFPA 101 CH 38 NEW BUSINESS |
| | |
| | 38.3.3.3 INTERIOR FLOOR FINISH. |
| | 38.3.3.3.1 INTERIOR FLOOR FINISH SHALL COMPLY WITH |
| | SECTION 10.2 |
| | |
| | 10.2.7.2* FLOOR COVERINGS, OTHER THAN CARPET FOR WHICH |
| | 10.2.2.2 |
| | ESTABLISHES REQUIREMENTS FOR FIRE PERFORMANCE, SHALL |
| | HAVE A |
| | MINIMUM CRITICAL RADIANT FLUX OF 0.1 W/CM2. |
| | |
| | FOR THE OFFICIAL RECORD, PLEASE PROVIDE THE FLOORING |
| | PRODUCT NAME AND THE PRODUCT SPEC SHEETS OF THE |
| | PROPOSED FINISHED FLOORING INDICATING THE FIRE BEHAVIOR |
| | RATING. |
| | |
| | |
| | |
| | 4) ELECTRICAL PLANS - THERE ARE NO CLEAR INDICATIONS OF |
| | EMERGENCY LIGHTING. |
| | |
| | PER NFPA 101 CH 38 |
| | |
| | 38.2.9 EMERGENCY LIGHTING. |
| | 38.2.9.1 EMERGENCY LIGHTING SHALL BE PROVIDED IN |
| | ACCORDANCE WITH SEC TION 7.9 IN ANY BUILDING WHERE ANY |
| | ONE OF THE FOLLOWING CONDITIONS EXISTS: |
| | (1) THE BUILDING IS THREE OR MORE STORIES IN HEIGHT. |
| | (2) THE OCCUPANCY IS SUBJECT TO 50 OR MORE OCCUPANTS |
| | ABOVE OR BELOW |
| | THE LEVEL OF EXIT DISCHARGE. |
| | (3) THE OCCUPANCY IS SUBJECT TO 300 OR MORE TOTAL |
| | OCCUPANTS |
| | |
| | PLEASE REVIEW AND CORRECT OR JUSTIFY OMISSION WITH |
| | SPECIFIC DETAILS. |
| | |
| | |
| | |
| | 5) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET |
| | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE |
| | ABOVE. |
| | |
| | |
| | 6) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE |
| | RE-SUBMITTAL OF THE ABOVE. |
| | |
| | |
| | PETER LEDUC |
| | FIRE MARSHAL |