| Plan Review Notes For Permit 22061421 |
| Permit Number |
22061421 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2022-08-17 09:27:47 | FLORIDA BUILDING CODE 2020 7TH EDITION | | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 7TH ED | | | NFPA 70 2017 EDITION | | | | | | JAKE LEAHY | | | ELECTRICAL PLANS EXAMINER II | | | 561-805-6713 | | | [email protected] | | | | | | 1) PLEASE INDICATE ON PLANS WHICH ROOMS SHALL BE WIRED | | | PER NEC 517.13, 517.18, 517.19 | | | | | | 2) PAGE E3.1 SERVICE MAIN IS SHOWN AS A 400A DISCONNECT | | | FEEDING A 200 AMPERE PANEL. | | | | | | 3) PROVIDE AVAILABLE SHORT CIRCUIT CALCULATION FOR | | | SERVICE INCLUDING INFORMATION FROM THE POWER COMPANY | | | STATING WHAT THE AVAILABLE SHORT CIRCUIT CURRENT IS FOR | | | THE SERVICE TO CONFIRM THE STATED AIC RATING OF THE | | | SERVICE EQUIPMENT IS ADEQUATE. NEC 110.9, 110.10; FBC | | | RE E3606.3 | | | | | | |
|