Plan Review Notes
Plan Review Notes For Permit 22061421
Permit Number 22061421
Review Stop B
Sequence Number 1
Notes
Date Text
2022-08-17 10:43:12WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION
 SERVICES/ BUILDING DIVISION
 2020 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 22061421
 ADD: 575 FERN ST. (360 S. ROSEMARY/ 21 STORY BUILDING)
 1ST TENANCY
 CONT: BLACK DIAMOND GENERAL CONTRACTING
 TEL: 561-746-3452
 E-MAIL: [email protected]
  
 2020 FLORIDA BUILDING CODE W 2020 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2020 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: WED. AUG. 17TH/2022
 ACTION: DENIED
  
 1) LIFE SAFETY PLAN:
 1A) THE OCCUPANCY LOAD SHOWN OF 36 PERSONS FROM TABLE
 1004.5 OF THE 2020 FBC-BUILDING CODE. THE OCCUPANT LOAD
 SHOWN ON THE LIFE SAFETY PLAN WILL BE OVER 50 PERSONS.
 PLEASE PROVIDE WHAT THE INCREASED OCCUPANT LOAD WILL BE
 IN ACCORDANCE WITH SECTION 1004.2 OF THE 2020
 FBC-BUILDING CODE.
  
 1B) HEADING CODE REQUIREMENTS. LIST THE REQUIREMENTS
 THAT 2 EXITS ARE REQUIRED, 3 PROVIDED. BECAUSE OF THE
 CLOSENESS OF THE 2 FRONT EXITS (LESS THAN 1/3RD OVERALL
 DIAGONAL DISTANCE APART) THE BACK EXIT THROUGH THE LAB
 IS A CONCERN. LOOKING AT THE BASE BUILDING PLAN FOR 360
 ROSEMARY THERE IS AN ELEVATED EXIT PASSAGEWAY THAT
 PASSES JUST BEHIND THIS TENANT SPACE, THE NORTH WALL OF
 THIS TENANT SPACE ROOMS 143 & 144. WHEN EXITING THROUGH
 THE LAB WHERE ARE YOU GOING, WHAT ROOM IS SHOWN HOW ARE
 YOU EXITING TO THE PUBLIC WAY. 2020 FBC-BUILDING CODE
 1007.1.1 & 1028.5.
  
 1C) THIS SAME EXIT PASSAGEWAY TO THE EXTERIOR OF THE
 BUILDING IS A 2-HOUR ENCLOSURE, THE BACK WALLS OF ROOMS
 143 & 144 IT APPEARS WOULD BE PART OF THE 2-HOUR
 ENCLOSURE. THE LEGEND SHOWS THE BACK WALL AS A 1-HOUR
 WALL. SECTION 1024.3 CONSTRUCTION IS THE SAME AS THE
 VERTICAL EXIT STAIRS, OVER4 STORIES 2 HOURS.
  
 1D) LIFE SAFETY PLAN & A1.12-DIMENSION PLAN.A1.11 DOOR
 TAGS. CLOSET DOORS 131, 132 & TOILET ROOM 111 (DOOR
 TAGS 36,37,& 38) IT APPEARS ARE OVER THE REQUIRED WIDTH
 OF THE CORRIDOR MORE THAN ONE-HALF. 1005.7.1. TABLE
 1020.2. CORRIDOR 44 INCHES X ?= 22 INCHES. 22 +36 = 58
 INCHES MIN. CORRIDOR WIDTH, CORRIDOR 133.
  
 1E)THE LIFE SAFETY PLAN NOR A1.12-DIMENSION FLOOR PLAN
 PROVIDE THE SQUARE FOOTAGE OF ROOM 123 DIRTY LAUNDRY
 STORAGE ROOM ASSUMED. TABLE 509 IN THE 2020 FBC-BUILD.
 CODE STATES LAUNDRY ROOMS OVER 100 SQ. FT. 1HR OR FIRE
 SPRINKLERS. PLEASE ALSO READ THE SECTION 509.4.2
 PROTECTION WALLS CAPABLE OF RESISTING SMOKE, WALLS
 SHALL EXTEND TO THE UNDERSIDE OF THE CEILING THAT IS A
 COMPONENT OF A FIRE RESISTANCE RATED FLOOR CEILING
 ASSEMBLY. DOORS SHALL BE SELF OR AUTOMATIC CLOSING.
  
 2) IF-300 TOILET ELEVATIONS. ELEVATION BACK WALL OF
 RESTROOM WITH W. C. DOES NOT SHOW COMPLIANCE WITH: 2020
 FBC-B 1210.2.2. WALLS & PARTITIONS. THIS COMMENT IS A
 RESULT OF THE BUILDING OFFICIAL INTERPRETATION ON
 06/2020. IN BATHROOMS, RESTROOMS & SERVICE SINK AREAS
 EPOXY PAINT IS NO LONGER CONSIDERED A SMOOTH HARD,
 NON-ABSORBENT SURFACE.
  
 2A) 1210.2.2 WALLS & PARTITIONS WITHIN 2 FEET OF
 SERVICE SINKS, URINALS, AND WATER CLOSETS SHALL HAVE A
 SMOOTH, HARD, NON-ABSORBENT SURFACE TO A HEIGHT OF NOT
 LESS THAN 4 FEET ABOVE THE FLOOR, EXCEPT FOR STRUCTURAL
 ELEMENTS, THE MATERIAL USED IN SUCH WALLS SHALL BE OF A
 TYPE THAT IS NOT ADVERSELY AFFECTED BY MOISTURE.
  
 2B) 2509.1. WET AREAS. SHOWERS AND PUBLIC TOILET WALLS
 SHALL COMPLY WITH 1210.2.
  
 2C) 1210.2. FINISH MATERIALS. WALLS, BASE, FLOORS AND
 PARTITIONS IN TOILET AND BATHROOMS SHALL COMPLY WITH
 SECTIONS 1210.1 THROUGH 1210.4.
  
 3) LIFE SAFETY PLAN NOR A1.12-DIMENSION PLAN SHOW THE
 X-RAY ROOM # 145 IN COMPLIANCE WITH SECTION 465 CONTROL
 OF RADIATION HAZARD
 3A) SHIELDING 465.5.1 SHIELDING.
 3B) 465.6 DOORS, INTERLOCK AND WARNING SYSTEMS
  
 4) A TRANSMITTAL LETTER / NARRATIVE LISTING THE
 ORIGINAL REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF
 THE REVISION MADE, IDENTIFYING THE SHEET OR
 SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND WILL
 HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR
 ANTICIPATED COOPERATION.22061353
  
 PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS
 REVIEW, SUBSEQUENT REMARKS MAYBE MADE IN THE NEXT
 REVIEW CYCLE.
  
 MY WORK HOURS ARE USUALLY TUES. & WED. 7:30 AM- 4:30 PM
 PART-TIME/ SEMI-RETIRED.
  
 IF YOU WISH TO SPEAK WITH A PLANS EXAMINER BEFORE I GET
 BACK INTO THE OFFICE CALL
 (561)805-6700 AND ASK FOR THE PLANS EXAMINER ON-CALL.
 THANK YOU.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  