| Notes |
| Date |
Text |
| 2022-07-15 16:17:21 | FLORIDA BUILDING CODE 2020 7TH EDITION | | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 7TH ED | | | NFPA 70 2017 EDITION | | | | | | JAKE LEAHY | | | ELECTRICAL PLANS EXAMINER II | | | 561-805-6713 | | | [email protected] | | | | | | THE TWO FEEDER TO THE PANELS ARE TOO SMALL PER TH | | | STATEMENT BELOW. SHOULD BE 3/0 310.15(B)(7) | | | | | | FOR A FEEDER RATED 100 THROUGH 400 AMPERES, THE FEEDER | | | CONDUCTORS SUPPLYING THE ENTIRE LOAD ASSOCIATED WITH A | | | ONE-FAMILY DWELLING, OR THE FEEDER CONDUCTORS SUPPLYING | | | THE ENTIRE LOAD ASSOCIATED WITH AN INDIVIDUAL DWELLING | | | UNIT | | | IN A TWO-FAMILY OR MULTIFAMILY DWELLING, SHALL BE | | | PERMITTED TO HAVE AN AMPACITY NOT LESS THAN 83 PERCENT | | | OF THE FEEDER | | | RATING. |
|