| 2023-01-11 09:09:11 | BUILDING ADDITION | | | REVIEWED BY ROGER MCPHERSON | | | 561-805-6716 | | | [email protected] | | | CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1 | | | AMENDMENT | | | | | | CORRECTIONS NEEDED - | | | | | | 1) THE SITE PLAN NEEDS TO SHOW STORM WATER DRAINAGE | | | AWAY FROM THE BUILDING AND AWAY FROM THE ADJACENT | | | PROPERTY OR PROVIDE A STORM WATER DRAINAGE PLAN FBC WPB | | | 107.2.5 SITE PLAN. THE CONSTRUCTION DOCUMENTS SUBMITTED | | | WITH THE APPLICATION FOR PERMIT SHALL BE ACCOMPANIED BY | | | A SITE PLAN SHOWING TO SCALE THE SIZE AND LOCATION OF | | | NEW CONSTRUCTION AND EXISTING STRUCTURES ON THE SITE, | | | DISTANCES FROM LOT LINES, THE ESTABLISHED STREET GRADES | | | AND THE PROPOSED FINISHED GRADES, DEPICTING THE | | | PROPOSED LOT DRAINAGE AND, AS APPLICABLE, FLOOD HAZARD | | | AREAS, FLOODWAYS, AND DESIGN FLOOD ELEVATIONS; AND IT | | | SHALL BE DRAWN IN ACCORDANCE WITH AN ACCURATE AND | | | INCLUDED ON A BOUNDARY LINE SURVEY. (PLEASE PROVIDE CUT | | | SECTIONS FOR ANY PROPOSED WATER RETAINING SWALES) | | | | | | 2) PLEASE PROVIDE A SURVEY. | | | | | | 3) DRAWING PSP-1 NEEDS TO BE SIGNED BY THE DESIGNER - | | | FBC WPB 107.1 | | | | | | | | | | | | | | | |
|