Plan Review Notes
Plan Review Notes For Permit 22061370
Permit Number 22061370
Review Stop FIRE
Sequence Number 4
Notes
Date Text
2022-11-21 09:44:47FIRE PROVISO COMMENTS:
  
 7.2.1.7 PANIC HARDWARE AND FIRE EXIT HARDWARE.
  
 7.2.1.7.1 WHERE A DOOR ASSEMBLY IS REQUIRED TO BE
 EQUIPPED
 WITH PANIC OR FIRE EXIT HARDWARE, SUCH HARDWARE SHALL
 MEET ALL
 OF THE FOLLOWING CRITERIA:
 (1) IT SHALL CONSIST OF A CROSS BAR OR A PUSH PAD, THE
 ACTUATING
 PORTION OF WHICH EXTENDS ACROSS NOT LESS THAN ONE-HALF
 OF
 THE WIDTH OF THE DOOR LEAF.
 (2) IT SHALL BE MOUNTED AS FOLLOWS:
 (A) NEW INSTALLATIONS SHALL BE NOT LESS THAN 34 IN.
 (865 MM),
 AND NOT MORE THAN 48 IN. (1220 MM), ABOVE THE FLOOR.
 (B) EXISTING INSTALLATIONS SHALL BE NOT LESS THAN 30
 IN.
 (760 MM), AND NOT MORE THAN 48 IN. (1220 MM),
 ABOVE THE FLOOR.
 (3) IT SHALL BE CONSTRUCTED SO THAT A HORIZONTAL FORCE
 NOT TO
 EXCEED 15 LBF (66 N) ACTUATES THE CROSS BAR OR PUSH PAD
 AND LATCHES.
 7.2.1.7.2* ONLY APPROVED FIRE EXIT HARDWARE SHALL BE
 USED ON
 FIRE PROTECTION-RATED DOOR ASSEMBLIES. NEW PANIC
 HARDWARE
 AND NEW FIRE EXIT HARDWARE SHALL COMPLY WITH ANSI/UL
 305,
 STANDARD FOR SAFETY PANIC HARDWARE, AND ANSI/BHMA
 A156.3,
 EXIT DEVICES.
 7.2.1.7.3 REQUIRED PANIC HARDWARE AND FIRE EXIT
 HARDWARE, IN
 OTHER THAN DETENTION AND CORRECTIONAL OCCUPANCIES AS
 OTHERWISE
 PROVIDED IN CHAPTERS 22 AND 23, SHALL NOT BE EQUIPPED
 WITH ANY LOCKING DEVICE, SET SCREW, OR OTHER
 ARRANGEMENT THAT
 PREVENTS THE RELEASE OF THE LATCH WHEN PRESSURE IS
 APPLIED TO
 THE RELEASING DEVICE.
 7.2.1.7.4 DEVICES THAT HOLD THE LATCH IN THE RETRACTED
 POSITION
 SHALL BE PROHIBITED ON FIRE EXIT HARDWARE, UNLESS SUCH
 DEVICES
 ARE LISTED AND APPROVED FOR SUCH A PURPOSE.
  