Plan Review Notes
Plan Review Notes For Permit 22061370
Permit Number 22061370
Review Stop FIRE
Sequence Number 3
Notes
Date Text
2022-09-27 10:29:16FIRE PROVISO COMMENTS:
 7.2.1.7 PANIC HARDWARE AND FIRE EXIT HARDWARE.
 7.2.1.7.1 WHERE A DOOR ASSEMBLY IS REQUIRED TO BE
 EQUIPPED WITH PANIC OR FIRE EXIT HARDWARE, SUCH
 HARDWARE SHALL MEET ALL OF THE FOLLOWING CRITERIA:
 (1) IT SHALL CONSIST OF A CROSS BAR OR A PUSH PAD, THE
 ACTUATING
 PORTION OF WHICH EXTENDS ACROSS NOT LESS THAN ONE-HALF
 OF
 THE WIDTH OF THE DOOR LEAF.
 (2) IT SHALL BE MOUNTED AS FOLLOWS:
 (A) NEW INSTALLATIONS SHALL BE NOT LESS THAN 34 IN.
 (865 MM),
 AND NOT MORE THAN 48 IN. (1220 MM), ABOVE THE FLOOR.
 (B) EXISTING INSTALLATIONS SHALL BE NOT LESS THAN 30
 IN.
 (760 MM), AND NOT MORE THAN 48 IN. (1220 MM),
 ABOVE THE FLOOR.
 (3) IT SHALL BE CONSTRUCTED SO THAT A HORIZONTAL FORCE
 NOT TO
 EXCEED 15 LBF (66 N) ACTUATES THE CROSS BAR OR PUSH PAD
 AND LATCHES.
 7.2.1.7.2* ONLY APPROVED FIRE EXIT HARDWARE SHALL BE
 USED ON FIRE PROTECTION-RATED DOOR ASSEMBLIES. NEW
 PANIC HARDWARE AND NEW FIRE EXIT HARDWARE SHALL COMPLY
 WITH ANSI/UL 305, STANDARD FOR SAFETY PANIC HARDWARE,
 AND ANSI/BHMA A156.3,
 EXIT DEVICES.
 7.2.1.7.3 REQUIRED PANIC HARDWARE AND FIRE EXIT
 HARDWARE, IN OTHER THAN DETENTION AND CORRECTIONAL
 OCCUPANCIES AS OTHERWISE PROVIDED IN CHAPTERS 22 AND
 23, SHALL NOT BE EQUIPPED WITH ANY LOCKING DEVICE, SET
 SCREW, OR OTHER ARRANGEMENT THAT PREVENTS THE RELEASE
 OF THE LATCH WHEN PRESSURE IS APPLIED TO THE RELEASING
 DEVICE.
 7.2.1.7.4 DEVICES THAT HOLD THE LATCH IN THE RETRACTED
 POSITION SHALL BE PROHIBITED ON FIRE EXIT HARDWARE,
 UNLESS SUCH DEVICES ARE LISTED AND APPROVED FOR SUCH A
 PURPOSE.
  