| Plan Review Notes For Permit 22061370 |
| Permit Number |
22061370 |
|
| Review Stop |
M |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2022-08-29 07:08:21 | 2ND REVIEW FMC | | | PERMIT: 22061370 | | | | | | CODES IN EFFECT: 2020 | | | | | | FBC- FLORIDA BUILDING CODE | | | FMC- FLORIDA MECHANICAL CODE | | | FEC- FLORIDA ENERGY CONSERVATION | | | FGC- FLORIDA FUEL GAS | | | FEX- FLORIDA EXISTING BUILDING CODE | | | FRC- FLORIDA RESIDENTIAL BUILDING CODE | | | F.S.- FLORIDA STATUTES | | | FAC- FLORIDA ACCESSIBILITY CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) ACCORDING TO THE LISTED SQ FT IN THE OUTDOOR AIR | | | CALCULATIONS ON SHEET M-20 THE OCCUPANT COUNT FOR THE | | | SEATING AREA, DINING ROOMS, SHOULD BE 165 WHICH WOULD | | | REQUIRE A TOTAL OF 2,077 CFM OF OUTDOOR AIR. THE ACTUAL | | | OCC. LOAD LISTED ON THE VENTILATION CHART IS 135. | | | PLEASE ADJUST THE OUTDOOR AIR CALCULATIONS TO REFLECT | | | THE ADDITIONAL REQUIRED OUTDOOR AIR FOR THIS AREA. FMC | | | 403.3.1.1 AND TABLE 403.3.1.1 | | | | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM. | | | | | | MICHAEL EDWARDS | | | MECHANICAL EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL. 33401 | | | 561-805-6728 | | | [email protected] | | | |
|