| Notes |
| Date |
Text |
| 2022-08-15 13:18:45 | THIS PLAN WAS FAILED BY C. WALKER, FIRE PREVENTION | | | DIVISION, WITH THE FOLLOWING COMMENTS: | | | | | | (1) PROVIDE A SITE PLAN. NFPA 1, 1.14 | | | | | | (2) EXIT DOORS FROM THE DINING ROOM SHALL BE EQUIPPED | | | WITH PANIC HARDWARE. NFPA 101, 12.2.2.2.3 | | | | | | (3) EMERGENCY LIGHTING LOCATIONS SHALL BE INDICATED ON | | | THE PLANS. NFPA 101, 12.2.9 | | | | | | (4) EXIT SIGN LOCATIONS SHALL BE INDICATED ON THE | | | PLANS. NFPA 12.2.10 | | | | | | (5) THE PLAN INDICATES THE BUILDING IS TO BE EQUIPPED | | | WITH FIRE SPRINKLERS. THE ENGINEERING DOCUMENTS MUST BE | | | INCLUDED WITH THE MATER PLAN PER FAC 61G15-30.003 | | | THE INSTALLATION OF A FIRE SPRINKLER SYSTEM WILL | | | REQUIRE A SEPARATE PERMIT AND SHOP DRAWINGS. | | | | | | (6) THE KITCHEN HOOD AND KITCHEN HOOD SUPPRESSION WILL | | | REQUIRE SEPARATE PERMITS AND SHOP DRAWINGS FOR | | | APPLIANCES PRODUCING GREASE LADEN VAPOR. NFPA 101, | | | 12.3.2.2 | | | | | | (7) OCCUPANT LOAD POSTING SHALL BE PROVIDED IN | | | ACCORDANCE WITH NFPA 101, 12.7.9.3 | | | | | | WHEN RESUBMITTING, INDICATE CHANGES WITH CLOUDING ON | | | THE APPLICABLE PLAN SHEETS OR RESPOND IN NARRATIVE | | | FORM. | | | | | | C. WALKER | | | | | | 561-804-4762 | | | | | | [email protected] | | | |
|