| 2022-07-21 11:12:55 | 1ST PLUMBING REVIEW |
| | |
| | V7 FPC - 2020 FLORIDA PLUMBING CODE |
| | V7 FGC - 2020 FLORIDA FUEL GAS |
| | V7 FRC - 2020 FLORIDA RESIDENTIAL BUILDING CODE |
| | V7 FAC - 2020 FLORIDA ACCESSIBILITY CODE |
| | V7 FEX - 2020 FLORIDA EXISTING BUILDING CODE |
| | V7 FEC - 2020 FLORIDA ENERGY CONSERVATION |
| | 2021 F.S. - 2021 FLORIDA STATUTES |
| | 2021 F.A.C. - 2021 FLORIDA ADMINISTRATIVE CODE |
| | 2017 WPB AMEND - 2017 WEST PALM BEACH AMENDMENTS TO THE |
| | FBC CHAPTER 1 |
| | |
| | THIS PLAN WAS REVIEWED FOR CODE COMPLIANCE AND FAILED |
| | BY RYAN BROWN WITH THE FOLLOWING COMMENTS. |
| | |
| | 1. 2020 FPC 1003.3.8 - PAGE P-4.0 - DETAIL NUMBER 7 - |
| | THE GREASE INTERCEPTOR DETIAL SHOWS AN INDIRECT |
| | CONNECTION. THE DISCHARGE FROM A GREASE INTERCEPTOR |
| | MUST BE DIRECTLY CONNECTED TO THE SANITARY SYSTEM. |
| | |
| | 2. 2020 FPC 909.2 - PAGE P-4.0 - DETAIL NUMBER 6 - THE |
| | DETAIL SHOWS A COMBO-WYE FITTING. THIS WOULD NEED TO BE |
| | A TEE FITTING OR THE VENT CONNECTION WILL BE BELOW THE |
| | TRAP WEIR. |
| | |
| | 3. 2017 WPB AMENDS 107.2.1 - THERE ARE TWO FLOOR DRAINS |
| | ON THE PLANS THAT SHOW A VENT RISING OUT OF THE FLOOR |
| | IN THE MIDDLE OF THE BAR AREA. PLEASE CORRECT. |
| | |
| | 4. 2020 FPC 607.1.1 - PLEASE SHOW COMPLIANCE WITH THE |
| | LIMIT FOR HOT WATER. THE THERMOSTAT ON THE WATER HEATER |
| | SHALL NOT BE THE LIMITING DEVICE FOR HOT WATER |
| | DELIVERY. |
| | |
| | 5. 2020 FPC 607.1.2/419.5 - PLEASE SHOW COMPLIANCE FOR |
| | THE LIMITING DEVICE REQUIRED FOR PUBLIC HANDWASHING |
| | FACILITIES AND TEMPERED WATER. THE DEVICE SHOULD |
| | CONFORM TO ASSE 1070. |
| | |
| | 6. 2017 WPB AMEND ? 107.3 -- A SEPARATE PERMIT IS |
| | REQUIRED FOR THE INTERCEPTOR. WHEN YOU OBTAIN THE |
| | PERMIT NUMBER FOR THE INTERCEPTOR, SUBMIT IT TO ME FOR |
| | RELEASE OF THIS COMMENT. |
| | |
| | 7. 2017 WPB AMEND ? 107.2.1 - PLEASE ADD YOUR GREASE |
| | CALCULATIONS FOR GI SIZING. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM. |
| | |
| | |