| 2022-07-19 13:30:21 | 1ST REVIEW FMC |
| | PERMIT: 22061370 |
| | |
| | CODES IN EFFECT: 2020 |
| | |
| | FBC- FLORIDA BUILDING CODE |
| | FMC- FLORIDA MECHANICAL CODE |
| | FEC- FLORIDA ENERGY CONSERVATION |
| | FGC- FLORIDA FUEL GAS |
| | FEX- FLORIDA EXISTING BUILDING CODE |
| | FRC- FLORIDA RESIDENTIAL BUILDING CODE |
| | F.S.- FLORIDA STATUTES |
| | FAC- FLORIDA ACCESSIBILITY CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) PROVIDE THE ENERGY CALCULATIONS. FEC101.5.1.1.2 |
| | |
| | 2) PROVIDE THE MECHANICAL EQUIPMENT SIZING |
| | CALCULATIONS. FEC 403.2.1 |
| | |
| | 3) PROVIDE OUTDOOR AIR CALCULATIONS FOR EACH USE OF |
| | SPACE IN THIS BUILDING; DINING, BAR, KITCHEN. FMC |
| | 403.3.1.1 AND TABLE 403.3.1.1 |
| | |
| | 4) ADD A NOTE ON THE MECHANICAL DRAWINGS STATING THAT |
| | THE REFRIGERATION WILL REQUIRE A SEPARATE PERMIT |
| | APPLICATION AND MECHANICAL REVIEW. |
| | |
| | 5) ADD A NOTE ON THE MECHANICAL DRAWINGS STATING THAT |
| | THE HOODS AND EXHAUST DUCT FOR THE HOODS WILL REQUIRE A |
| | SEPARATE PERMIT APPLICATION AND MECHANICAL REVIEW. |
| | |
| | 6) PROVIDE THE KITCHEN EQUIPMENT SCHEDULE. FBC 107.2.1 |
| | |
| | 7) PROVIDE A DETAIL OF THE CONDENSING UNITS LOCATION |
| | AND ANCHORAGE. FBC 107.2.1 |
| | |
| | |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM. |
| | |
| | MICHAEL EDWARDS |
| | MECHANICAL EXAMINER |
| | 401 CLEMATIS STREET |
| | WEST PALM BEACH FL. 33401 |
| | 561-805-6728 |
| | [email protected] |
| | |