| Plan Review Notes For Permit 22061370 |
| Permit Number |
22061370 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2022-07-05 14:56:39 | FIRE REVIEW COMMENTS: | | | PROVIDE A SITE PLAN. NFPA 1, 1.14 | | | EXIT DOORS FROM THE DINING ROOM SHALL BE EQUIPPED WITH | | | PANIC HARDWARE. NFPA 101, 12.2.2.2.3 | | | EMERGENCY LIGHTING LOCATIONS SHALL BE PROVIDED ON THE | | | LIFE SAFETY PLAN. NFPA 101, 12.2.9 | | | EXIT SIGN LOCATIONS SHALL BE INDICATED ON THE LIFE | | | SAFETY PLAN. NFPA 101, 12.2.10 | | | THE LIFE SAFETY PLAN INDICATES THE BUILDING IS A | | | SPRINKLERED. THE ENGINEERING DOCUMENTS MUST BE INCLUDED | | | WITH THE MASTER PLAN PER FAC 61G15-30.003 | | | THE INSTALLATION OF A FIRE SPRINKLER SYSTEM WILL ALSO | | | REQUIRE A SEPARATE PERMIT AND SHOP DRAWINGS. | | | THE KITCHEN HOOD AND THE KITCHEN HOOD FIRE SUPPRESSION | | | WILL REQUIRE SEPARATE PERMITS AND SHOP DRAWINGS FOR | | | APPLIANCES PRODUCING GREASE LADEN VAPOR. NFPA 101 | | | 12.3.2.2 | | | OCCUPANT LOAD POSTING SHALL BE PROVIDED IN ACCORDANCE | | | WITH NFPA 101 12.7.9.3 | | | C. WALKER | | | 561-804-4762 | | | [email protected] | | | |
|