| Plan Review Notes For Permit 22061370 |
| Permit Number |
22061370 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2022-08-03 13:04:39 | FLORIDA BUILDING CODE 2020 7TH EDITION | | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 7TH ED | | | NFPA 70 2017 EDITION | | | | | | JAKE LEAHY | | | ELECTRICAL PLANS EXAMINER II | | | 561-805-6713 | | | [email protected] | | | | | | 1) FAULT CURRENT RATING OF THE MAIN AND PANELS REQUIRED | | | PER 110.21. | | | | | | 2) PLEASE DESIGNATE THE KITCHEN AREA ON ELECTRICAL | | | PLAN. | | | | | | 3) FLOOR OUTLETS IN BAR AREA? THIS IS CONSIDERED A WET | | | LOCATION PLEASE SHOW DETAIL OF HOW OUTLETS WILL BE | | | LISTED FOR LOCATON. 110.3 | | | | | | 4) GFCI PROTECTION HAS CHANGED IN THE 2017 NEC PLEASE | | | SEE THE PLAN FOR ADDITIONAL AREAS WERE PROTECTION IS | | | REQUIRED. |
|