| 2022-08-05 14:30:07 | BUILDING ADDITION |
| | REVIEWED BY ROGER MCPHERSON |
| | 561-805-6716 |
| | [email protected] |
| | CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1 |
| | AMENDMENT |
| | |
| | CORRECTIONS NEEDED - |
| | |
| | 1) SEPARATE PERMIT IS REQUIRED FOR THE BUILDING DEMO. |
| | |
| | 2) PLEASE PROVIDE COMPLETE (FRONT PAGES AND THE |
| | INSTALLATION INSTRUCTIONS) MIAMI DADE OR FLORIDA STATE |
| | PRODUCT APPROVAL FOR THE EXTERIOR WINDOWS, DOORS AND |
| | ROOFING SYSTEMS - ALL PRODUCT APPROVALS NEED TO BE |
| | REVIEWED AND MARKED APPROVED BY THE BUILDING DESIGNER |
| | OF RECORD FBC WPB 107.3.4 |
| | |
| | 3) PLEASE PROVIDE THE FOUNDATION/WALL ATTACHMENT TO |
| | EXISTING FOUNDATION DRAWINGS. FBC WPB 107.2 |
| | |
| | 4) UNABLE TO FIND THE COLUMN SCHEDULE. FBC WPB 107.2 |
| | |
| | 5) DRAWING S1 SHOWS CUT SECTIONS REFERRING TO DRAWING |
| | S4 - I DO NOT SEE DRAWING S4 IN PROJECTDOX. |
| | |
| | 6) DRAWING S1 DETAIL 1 SHOWS ROOF SHEATHING ATTACHMENT |
| | TO STEEL JOIST - PLEASE SHOW ROOF SHEATHING ATTACHMENT |
| | TO THE WOOD JOIST. FBC 2304.10 |
| | |
| | 7) DOOR SCHEDULE IS NOT COMPLETE - FLOOR PLAN SHOWS |
| | MORE NUMBERED DOORS THEN WHAT IS SHOWN ON THE DOOR |
| | SCHEDULE. |
| | |
| | 8) PLEASE PROVIDE A WINDOW SCHEDULE - SHOW THE WINDOW |
| | TYPE, SIZE ETC. ROOF DORMERS SHOW WINDOWS. |
| | |
| | 9) PLEASE PROVIDE ROOF WIND ZONES AND PRESSURES - FBC |
| | 1609 |
| | |
| | 10) PLEASE SHOW THE ACCESSIBLE DINING LOCATIONS - FBC |
| | 226.1 GENERAL. |
| | WHERE DINING SURFACES ARE PROVIDED FOR THE CONSUMPTION |
| | OF FOOD OR DRINK, AT LEAST 5 PERCENT OF THE SEATING |
| | SPACES AND STANDING SPACES AT THE DINING SURFACES SHALL |
| | COMPLY WITH 902. |
| | |
| | 11) PLEASE SHOW THE ACCESSIBLE BAR SEATING LOCATION - |
| | SHOW COUNTER HEIGHT, KNEE AND TOE CLEARANCES - FBC A |
| | 226.2 DISPERSION. |
| | DINING SURFACES AND WORK SURFACES REQUIRED TO COMPLY |
| | WITH 902 SHALL BE DISPERSED THROUGHOUT THE SPACE OR |
| | FACILITY CONTAINING DINING SURFACES - FBC A 305.4KNEE |
| | AND TOE CLEARANCE. FBC A 902.3 HEIGHT. |
| | THE TOPS OF DINING SURFACES AND WORK SURFACES SHALL BE |
| | 28 INCHES (710 MM) MINIMUM AND 34 INCHES (865 MM) |
| | MAXIMUM ABOVE THE FINISH FLOOR OR GROUND. |
| | |
| | 12) PLEASE SHOW THE ACCESSIBLE PATH FROM THE ACCESSIBLE |
| | PARKING TO THE ACCESSIBLE ENTRY - FBC A 206.2.1 SITE |
| | ARRIVAL POINTS. |
| | AT LEAST ONE ACCESSIBLE ROUTE SHALL BE PROVIDED WITHIN |
| | THE SITE FROM ACCESSIBLE PARKING SPACES AND ACCESSIBLE |
| | PASSENGER LOADING ZONES; PUBLIC STREETS AND SIDEWALKS; |
| | AND PUBLIC TRANSPORTATION STOPS TO THE ACCESSIBLE |
| | BUILDING OR FACILITY ENTRANCE THEY SERVE. |
| | |
| | 13) PLEASE PROVIDE A SURVEY/SITE PLAN SHOWING THE |
| | FOLLOWING INFORMATION FBC WPB 107.2.5 SITE PLAN. THE |
| | CONSTRUCTION DOCUMENTS SUBMITTED WITH THE APPLICATION |
| | FOR PERMIT SHALL BE ACCOMPANIED BY A SITE PLAN SHOWING |
| | TO SCALE THE SIZE AND LOCATION OF NEW CONSTRUCTION AND |
| | EXISTING STRUCTURES ON THE SITE, DISTANCES FROM LOT |
| | LINES, THE ESTABLISHED STREET GRADES AND THE PROPOSED |
| | FINISHED GRADES, DEPICTING THE PROPOSED LOT DRAINAGE |
| | AND, AS APPLICABLE, FLOOD HAZARD AREAS, FLOODWAYS, AND |
| | DESIGN FLOOD ELEVATIONS; AND IT SHALL BE DRAWN IN |
| | ACCORDANCE WITH AN ACCURATE AND INCLUDED ON A BOUNDARY |
| | LINE SURVEY. (PLEASE PROVIDE CUT SECTIONS FOR ANY |
| | PROPOSED WATER RETAINING SWALES) |
| | |
| | 14) PLEASE PROVIDE A SURVEY. |
| | |
| | 15) PLEASE PROVIDE THE ALUMINUM CANOPY DETAILS - FBC |
| | 1609 |
| | |
| | 16) CANOPY DETAILS, ROOFING SYSTEMS, WINDOW AND DOOR |
| | PRODUCT APPROVALS MAY BE DEFERRED SUBMITTALS BY LISTING |
| | ITEMS TO BE DEFERRED ON THE CONSTRUCTION DOCUMENTS - |
| | FBC WPB 107.3.4.1 DEFERRED SUBMITTALS. FOR THE PURPOSES |
| | OF THIS SECTION, DEFERRED SUBMITTALS ARE DEFINED AS |
| | THOSE PORTIONS OF THE DESIGN THAT ARE NOT SUBMITTED AT |
| | THE TIME OF THE APPLICATION AND THAT ARE TO BE |
| | SUBMITTED TO THE BUILDING OFFICIAL WITHIN A SPECIFIED |
| | PERIOD. DEFERRAL OF ANY SUBMITTAL ITEMS SHALL HAVE THE |
| | PRIOR APPROVAL OF THE BUILDING OFFICIAL. THE REGISTERED |
| | DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE SHALL LIST |
| | THE DEFERRED SUBMITTALS ON THE CONSTRUCTION DOCUMENTS |
| | FOR REVIEW BY THE BUILDING OFFICIAL. DOCUMENTS FOR |
| | DEFERRED SUBMITTAL ITEMS SHALL BE SUBMITTED TO THE |
| | REGISTERED DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE |
| | WHO SHALL REVIEW THEM AND FORWARD THEM TO THE BUILDING |
| | OFFICIAL WITH A NOTATION INDICATING THAT THE DEFERRED |
| | SUBMITTAL DOCUMENTS HAVE BEEN REVIEWED AND FOUND TO BE |
| | IN GENERAL CONFORMANCE TO THE DESIGN OF THE BUILDING. |
| | THE DEFERRED SUBMITTAL ITEMS SHALL NOT BE INSTALLED |
| | UNTIL THE DEFERRED SUBMITTAL DOCUMENTS HAVE BEEN |
| | APPROVED BY THE BUILDING OFFICIAL. |
| | |