| 2022-09-14 11:16:29 | WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL |
| | MANUAL REVISED 2017 |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 |
| | 7TH EDITION |
| | FBC ACC = FLORIDA ACCESSIBILITY CODE 2020 7TH EDITION |
| | FBC EX = FLORIDA EXISTING BUILDING CODE 2020 7TH |
| | EDITION |
| | FBC PL = FLORIDA PLUMBING CODE 2020 7TH EDITION |
| | FAC= FLORIDA ADMINISTRATIVE CODE |
| | FS = FLORIDA STATUTES |
| | |
| | 22061364 3171 S DIXIE HWY |
| | |
| | 1ST REVIEW |
| | |
| | GENERAL: ELECTRONIC SIGNATURES ARE NOT VALID. |
| | |
| | PLUMBING COMMENTS: DENIED |
| | |
| | 1. PER FBC ACC 603.3, MIRROR SHALL BE A MAXIMUM OF 40 |
| | INCHES TO THE BOTTOM OF THE REFLECTING SURFACE. |
| | |
| | 2. A SHUT OFF VALVE SHALL BE PROVIDED ON THE COLD WATER |
| | SUPPLY TO THE WATER HEATER BETWEEN THE FIXTURE SUPPLY |
| | AND THE WATER HEATER. FBC PL 503.1 |
| | |
| | 3. ALL COMPONENTS IN THE DOMESTIC WATER SYSTEM SHALL BE |
| | LEAD FREE IN ACCORDANCE WITH FBC PL 605.2 AND 605.2.1. |
| | |
| | 4. PER WPB FBC 107.2.1, PROVIDE PIPE HANGER DETAIL WITH |
| | A NOTE STATING "HORIZONTAL PIPE SHALL BE SUPPORTED IN |
| | ACCORDANCE WITH FBC PL TABLE 308.5". |
| | |
| | 5. SANITARY RISER: PER WPB FBC 107.2.1, PROVIDE SIZING |
| | FOR COMMON VENT AND BRANCH FOR DRINKING FOUNTAIN AND |
| | MOP SINK (FBC PL 911.3 AND TABLE 911.3) AND FOR |
| | INDIVIDUAL AND BRANCH VENTS. |
| | |
| | 6. PROVIDE A PLUMBING FIXTURE SCHEDULE NOTING WATER |
| | SUPPLY AND DRAIN/TRAP CONNECTION SIZE |
| | |
| | |
| | |
| | END OF COMMENTS. |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID |
| | THE PREVIOUSLY REVIEWED SHEETS. ALL PLANS TO BE SIGNED |
| | AND SEALED BY THE DESIGNER AS REQUIRED BY FAC AND FS. |
| | |
| | |
| | |