| 2022-07-20 15:44:32 | 1ST REVIEW FBC-2020 PLUMBING |
| | PERMIT- 22061363 |
| | 7/20/2022 |
| | |
| | CODES IN EFFECT: |
| | FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020 |
| | FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION |
| | 2020 |
| | FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) SHEETS 1.0A, 3.0P, & 3.1P: THE FLOOR PLAN INDICATES |
| | A KITCHEN DISPLAY HOWEVER THE KITCHEN SINK AND |
| | DISHWASHER ARE BEING DRAINED INTO THE SANITARY SYSTEM. |
| | PLEASE NOTE IF THE KITCHEN WILL BE USED FOR COOKING AND |
| | FOOD PREPARATION THEN A GREASE INTERCEPTOR WILL BE |
| | REQUIRED- SEC. 1003.3.1 FBC P. PLEASE PROVIDE MORE |
| | INFORMATION ON THE PLANS. |
| | |
| | 2) 3.1P: THE SCHEDULE SHOWS A RECIRCULATION PUMP BUT |
| | THE RISER DOES NOT SHOW THE PUMP LOCATION OR THE HW |
| | RETURN LINE- SEC. 607.2 FBC P. |
| | |
| | 3) 3.1P: A LIMITING DEVICE FOR CONTROLLING THE HOT |
| | WATER TEMPERATURE AT THE KITCHEN SINK AND MOP SINK IS |
| | REQUIRED PER SEC. 607.1.1 FBC P. PLEASE PROVIDE EITHER |
| | A MASTER THERMOSTATIC MIXING VALVE OR POINT OF USE |
| | DEVICES AT THE SINKS. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |