Date Text
2022-08-06 11:13:20****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 2ND REVIEW IS INCLUDED BELOW FOR REFERENCE.
  
 PREVIOUS REVIEW COMMENT #3, # 5 - THE CIVIL PAGE WITH
 STRUCTURAL INFORMATION IS STILL NOT SIGNED AND SEALED.
 BUILDING OFFICIAL HAS REVIEWED THIS DOCUMENT AND IF
 STRUCTURAL INFORMATION IS SHOWN AND SPECIFIED, IT NEEDS
 TO BE SIGNED AND SEALED AS AN UNLICENSED INDIVIDUAL
 (FS471, FS481) CANNOT SPECIFY THIS INFORMATION. THIS
 CAN BE REQUESTED TO BE DELETED, BUT THEN THE OTHER SITE
 PLAN NEEDS TO BE REVISED TO SHOW LENGTH OF WALL.
  
 PREVIOUS REVIEW COMMENT #1 - THE ENGINEERING CALCS
 STILL REFER TO ASCE7-10. IF ENGINEER WANTS TO PROPOSE
 USING THIS OUTDATED REFERENCE (FBC B SPECIFIES USE OF
 ASCE7-16) HE NEEDS TO SUBMIT A LETTER ADDRESSED TO THE
 BUILDING OFFICIAL FOR CONSIDERATION.
  
 AFTER REVIEWS HAVE PASSED, A PAPER ORIGINAL WILL BE
 REQUIRED. THIS CAN BE A PROVISO ITEM.
  
 PREVIOUS LIST:
  
 1. ORIGINAL COMMENT - FBC B 1609, REVISE PLAN TO
 INCLUDE WIND DESIGN CRITERIA.
  
 2ND REVIEW, AN EMAIL WITHIN THE CALCULATIONS WAS
 INCLUDED WHICH STATED TO USE 54.0 PSF. PLEASE REVISE TO
 CLARIFY PER FBC B 1603.1.4 WHICH STATES THAT "THE
 FOLLOWING INFORMATION RELATED TO WIND LOADS SHALL BE
 SHOWN" - ULTIMATE WIND SPEED, NOMINAL WIND SPEED, RISK
 CATEGORY, WIND EXPOSURE, CLADDING.
  
 THIS APPEARS TO BE EXPOSURE D - IF ENGINEER HAS
 DESIGNED TO A DIFFERENT EXPOSURE CLASSIFICATION, PLEASE
 HAVE HIM EMAIL ME PRIOR TO RESUBMITTING TO DISCUSS.
  
 THE ENGINEER STATES THAT ASCE7-10 WAS USED FOR THE
 DESIGN. SEE FBC B CHAPTER 35, ASCE7-16 IS REQUIRED.
  
 2. ORIGINAL COMMENT - FBC B 1612, IT IS NOT CLEAR WHICH
 FLOOD ZONE THE PROPOSED WALL IS LOCATED IN. THE
 PROPOSED WALL IS TO EITHER MEET OUR FREEBOARD OF 2, OR
 IT IS TO BE DESIGNED TO RESIST FLOOD LOADS UP TO BASE
 FLOOD ELEVATION PLUS 2'. WHEN REVISING THE PLAN, BE
 CLEAR IF THE ELEVATIONS SPECIFIED ARE NGVD29 OR NAVD88.
  
 2ND REVIEW, BUILDING OFFICIAL HAS DETERMINED THAT
 FREEBOARD DOES NOT NEED TO APPLY. MY CONVERSATIONS WITH
 MICHAEL SPRUCE, PE INDICATED THAT HE IS AWARE THAT THIS
 NEEDS TO RESIST FLOOD LOADS TO BASE FLOOD ELEVATION OF
 WHAT APPEARS TO BE 7' (FLOOD LINE IS NOT SHOWN BUT
 APPEARS TO BE 7' NAVD88). I WAS UNABLE TO LOCATE
 RESISTANCE TO FLOOD LOADS ADDRESSED ON THE STRUCTURAL
 ENGINEER'S PLANS. THE STRUCTURAL ENGINEER NEEDS TO
 INCORPORATE THIS DESIGN CRITERIA INTO HIS PLAN, SEE FBC
 B 1612.4 WHICH STATES:
  
 1612.4 DESIGN AND CONSTRUCTION.
 THE DESIGN AND CONSTRUCTION OF BUILDINGS AND STRUCTURES
 LOCATED IN FLOOD HAZARD AREAS, INCLUDING COASTAL HIGH
 HAZARD AREAS AND COASTAL A ZONES, SHALL BE IN
 ACCORDANCE WITH CHAPTER 5 OF ASCE 7 AND WITH ASCE 24.
  
 REVISE PLAN TO SHOW COMPLIANCE. THE ENGINEERING SHOULD
 INCLUDE THE ELEVATIONS AND SHOULD INDICATE COMPLIANCE
 TO DESIGN FLOOD ELEVATION. SEE ASCE-24 SECTION 1.5.
  
 3. FBC 107, REVISE THE PLAN TO CLARIFY WALL LENGTH.
  
 2ND REVIEW ? ADDRESSED; SEE ITEM 5 BELOW. IF THIS PAGE
 IS REMOVED THE INFORMATION SHOULD BE INCORPORATED INTO
 THE SITE PLAN.
  
 4. DOCUMENTS PREPARED BY AN ENGINEER AND SUBMITTED FOR
 PUBLIC RECORD ARE TO BE SIGNED, SEALED, DATED
 ORIGINALS. PLEASE UPLOAD DIGITALLY SIGNED PLANS. IF THE
 ENGINEER DOES NOT HAVE A DIGITAL SIGNATURE, PLEASE HAVE
 HIM SEND ME AN EMAIL SO WE CAN DISCUSS OPTIONS.
  
 2ND REVIEW - SINCE THE ENGINEER ACKNOWLEDGES THAT HE
 DOES NOT HAVE A DIGITAL SIGNATURE, ORIGINAL PAPER
 SIGNED AND SEALED ENGINEERING WILL BE REQUIRED AFTER
 ALL REVIEWS HAVE PASSED. A SCAN OF SIGNED AND SEALED
 ENGINEERING IS NOT CONSIDERED ?ORIGINAL ENGINEERING? BY
 FLORIDA BOARD OF PROFESSIONAL ENGINEERS, SEE FLORIDA
 ADMINISTRATIVE CODE 61G15-23.002.
  
 NEW COMMENT:
  
 5. FLORIDA STATUTE 471, A NEW PAGE WAS SUBMITTED NAMED
 "FLAGLER TOWERS - MOCKUP LOCATION". THIS PAGE PROVIDES
 STRUCTURAL INFORMATION, THEREFORE SHOULD BE PREPARED BY
 A DESIGN PROFESSIONAL. EITHER HAVE THIS PAGE SIGNED AND
 SEALED, AND INCLUDE THE TITLE BLOCK OF THE ENGINEER
 TAKING RESPONSIBILITY FOR THE DESIGN, OR INCORPORATE
 THE INFORMATION INTO THE STRUCTURAL DRAWINGS PREPARED
 BY THE ENGINEER. THE SITE PLAN WHICH SIMPLY SHOWS THE
 LOCATION IS OK, BUT THE NEW PAGE INCLUDES STRUCTURAL
 AND FLOOD RELATED INFORMATION. IT APPEARS THAT THIS
 PAGE IS TO SHOW COMPLIANCE WITH FBC B 1612.4, BUT IS
 NOT PREPARED BY A DESIGN PROFESSIONAL, AND DOES NOT
 STATE THAT IT WILL RESIST FLOOD LOADS TO 7? NAVD88,
 ONLY STATES THAT THE TOP OF THE FOOTER WILL BE AT 7?.
  
  