| Plan Review Notes For Permit 22061347 |
| Permit Number |
22061347 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2022-06-29 12:55:56 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE | | | MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | | | 1) THERE IS A A SITE PLAN INDICATION OF A GENERAL | | | LOCATION OF A MOCK WALL, HOWEVER, THERE ARE NO DETAILS | | | INCLUDING DIMENSIONS OF THE EXACT LOCATION OF THE WALL. | | | | | | FOR THE OFFICIAL RECORD, PLEASE PROVIDE SPECIFIC | | | LOCATION DETAILS INCLUDING DIMENSION TO NEARBY | | | STRUCTURES, OBJECTS, & EXIT DOORS. | | | | | | 1.7.12 PLANS AND SPECIFICATIONS. | | | | | | 1.7.12.1 THE AHJ SHALL HAVE THE AUTHORITY TO REQUIRE | | | PLANS AND SPECIFICATIONS TO ENSURE COMPLIANCE WITH | | | APPLICABLE CODES AND STANDARDS. | | | | | | 1.7.12.6 PLANS SHALL BE SUBMITTED TO THE AHJ PRIOR TO | | | THE ALTERATION OF THE MEANS OF EGRESS OR FIRE | | | PROTECTION SYSTEMS OF ANY EXISTING BUILDING. | | | | | | PLEASE REVIEW ENSURE AND PROVIDE ACCURATE DINMESIONS | | | THAT EGRESS AND EGRESS PATHS ARE NOT OBSTUCTED NOR | | | INTERFERE WITH THE PATH OF TRAVEL. | | | | | | | | | | | | 2) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET | | | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE | | | ABOVE. | | | | | | | | | 3) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE | | | RE-SUBMITTAL OF THE ABOVE. | | | | | | | | | PETER LEDUC | | | FIRE MARSHAL | | | 561-804-4709 | | | [email protected] | | | |
|