| 2022-07-19 18:49:49 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6724 | | | | | | FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020) | | | FBC B = FBC BUILDING | | | FBC EB = FBC EXISTING BUILDING | | | FBC A = FBC ACCESSIBILITY | | | FBC EC = FBC ENERGY CONSERVATION | | | FBC R = FBC RESIDENTIAL | | | | | | 1. FBC B 1609, REVISE PLAN TO INCLUDE WIND DESIGN | | | CRITERIA. | | | | | | 2. FBC B 1612, IT IS NOT CLEAR WHICH FLOOD ZONE THE | | | PROPOSED WALL IS LOCATED IN. THE PROPOSED WALL IS TO | | | EITHER MEET OUR FREEBOARD OF 2, OR IT IS TO BE DESIGNED | | | TO RESIST FLOOD LOADS UP TO BASE FLOOD ELEVATION PLUS | | | 2'. WHEN REVISING THE PLAN, BE CLEAR IF THE ELEVATIONS | | | SPECIFIED ARE NGVD29 OR NAVD88. | | | | | | 3. FBC 107, REVISE THE PLAN TO CLARIFY WALL LENGTH. | | | | | | 4. DOCUMENTS PREPARED BY AN ENGINEER AND SUBMITTED FOR | | | PUBLIC RECORD ARE TO BE SIGNED, SEALED, DATED | | | ORIGINALS. PLEASE UPLOAD DIGITALLY SIGNED PLANS. IF THE | | | ENGINEER DOES NOT HAVE A DIGITAL SIGNATURE, PLEASE HAVE | | | HIM SEND ME AN EMAIL SO WE CAN DISCUSS OPTIONS. | | | |
|