| 2022-08-24 05:46:43 | 2ND REVIEW FMC |
| | PERMIT: 22061327 |
| | |
| | CODES IN EFFECT: 2020 |
| | |
| | FBC- FLORIDA BUILDING CODE |
| | FMC- FLORIDA MECHANICAL CODE |
| | FEC- FLORIDA ENERGY CONSERVATION |
| | FGC- FLORIDA FUEL GAS |
| | FEX- FLORIDA EXISTING BUILDING CODE |
| | FRC- FLORIDA RESIDENTIAL BUILDING CODE |
| | F.S.- FLORIDA STATUTES |
| | FAC- FLORIDA ACCESSIBILITY CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) THERE IS A CLOSET THAT HAS A NOTE; THIS AEA NO |
| | RETURN DUE TO POSSIBLE CHEMICALS. WHAT KIND OF |
| | CHEMICALS ARE STORED IN THIS CLOSET? IS THERE A NEED TO |
| | PROVIDE EXHAUST IN THIS CLOSET FOR THE CHEMICALS? IF SO |
| | PLEASE REVISE THE DRAWING TO INCLUDE THE FAN, CFM, AND |
| | EXHAUST DUCT REQUIRED. FBC 107.3.5 |
| | |
| | 2) PROVIDE COMPLETE OUTDOOR AIR CALCULATIONS FOR EACH |
| | USE OF SPACE IN THIS TENANT SPACE. FMC 403.3.1.1 AND |
| | TABLE 403.3.1.1 |
| | |
| | 3) THE REVISION IS FOR DUCTING THE RETURN BACK TO THE |
| | AHU. AHU-2 DOES NOT HAVE THE DUCTED RETURN. PLEASE |
| | CLARIFY THIS DETAIL. FBC 107.3.5 |
| | |
| | 4) THE SCOPE OF WORK ON THE AC-1 SHEET INDICATES DIRTY |
| | ROOMS AND CLEAN ROOMS PLEASE IDENTIFY EACH ROOM. FBC |
| | 107.3.5 |
| | |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM. |
| | |