| Plan Review Notes For Permit 22061315 |
| Permit Number |
22061315 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2022-08-29 16:55:32 | FLORIDA BUILDING CODE 2020 7TH EDITION | | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 7TH ED | | | NFPA 70 2017 EDITION | | | | | | JAKE LEAHY | | | ELECTRICAL PLANS EXAMINER II | | | 561-805-6713 | | | [email protected] | | | | | | BREAKER TOO SMALL NEEDS TO BE AT LEAST A 50A BREAKER. | | | | | | 625.41 OVERCURRENT PROTECTION. | | | | | | OVERCURRENT PROTECTION FOR FEEDERS AND BRANCH CIRCUITS | | | SUPPLYING EQUIPMENT SHALL BE SIZED FOR CONTINUOUS DUTY | | | AND SHALL HAVE A RATING OF NOT LESS THAN 125 PERCENT OF | | | THE MAXIMUM LOAD OF THE EQUIPMENT. WHERE NONCONTINUOUS | | | LOADS ARE SUPPLIED FROM THE SAME FEEDER, THE | | | OVERCURRENT DEVICE SHALL HAVE A RATING OF NOT LESS THAN | | | THE SUM OF THE NONCONTINUOUS LOADS PLUS 125 PERCENT OF | | | THE CONTINUOUS LOADS. | | | | | | |
|