| Plan Review Notes For Permit 22061296 |
| Permit Number |
22061296 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2022-06-28 14:56:53 | THIS MUST COME IN AS A REVISION TO THE MASTER | | | PERMIT-20081382 AND NOT A STAND ALONE MECHANICAL | | | PERMIT. | | | THE DESIGNER MUST PROVIDE DEMO DRAWINGS OF THE SHAFT | | | AND THE DESIGN DRAWING SHOWING A CODE COMPLIANT SHAFT. | | | THE MECHANICAL DESIGNER MUST PROVIDE A DEMO DRAWING OF | | | THE ORIGINAL DESIGN OF THE DUCTWORK THAT IS INSIDE OF | | | THE SHAFT. THIS SHOULD ALSO NAME THE DUCTWORK AND | | | DETAIL THE USE OF THE DUCTWORK IN THE SHAFT. | | | THE DESIGNER MUST ALSO SHOW A DRAWING WITH ALL OF THE | | | DUCTWORK PUT BACK AS IT WAS ORIGINALLY AND IDENTIFYING | | | EACH DUCT INSIDE THE SHAFT. | | | THE UL SHAFT DETAIL SHOULD NOT BE ON THE MECHANICAL | | | DRAWING AS THIS SHOULD BE ON THE BUILDING DRAWING AS | | | THE GENERAL CONTRACTOR IS RESPONSIBLE FOR THE SHAFT. | | | | | | MICHAEL EDWARDS | | | MECHANICAL EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL. 33401 | | | 561-805-6728 | | | [email protected] | | | |
|