| Plan Review Notes For Permit 22061279 |
| Permit Number |
22061279 |
|
| Review Stop |
FIRE |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2022-08-15 10:22:44 | FIRE REVIEW COMMENTS: | | | | | | THE SUBMITTED INFORMATION IS FOR THE UNDERLAYMENT ONLY. | | | | | | PROVIDE THE SPECIFICATIONS ON THE TESTING FOR THE FIRE | | | PERFORMANCE OF THE FINISHED FLOORING MATERIALS | | | INCLUDING THE CRITICAL RADIANT FLUX. NFPA 101, 10.2.7 | | | | | | C. WALKER | | | | | | 561-804-4762 | | | | | | [email protected] | | | |
|