| 2022-09-07 15:41:04 | THE SITE PLAN INDICATES THAT IT IS WITHIN 11 FT OF THE |
| | BUILDING. |
| | |
| | THE PREVIOUS COMMENTS ARE RESUBMITTED. |
| | |
| | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE |
| | MARSHAL, WITH THE FOLLOWING COMMENTS: |
| | |
| | 1) ACCORDING TO THE SITE PLAN THE TRAILER IS TO BE |
| | SPEARATED BY AT LEAST 30'. |
| | |
| | PER NFPA 241, 4.2 TEMPORARY OFFICES AND SHEDS; TABLE |
| | 4.2.1 SEPARATION DISTANCES, FIRE SPRINKLERS ARE |
| | REQUIRED IN EACH TRAILER. |
| | 4.2.1* SEPARATION DISTANCES BETWEEN BUILDINGS UNDER |
| | CONSTRUCTION AND CONSTRUCTION-RELATED STRUCTURES, SUCH |
| | AS TEMPORARY OFFICES, TRAILERS, SHEDS, AND OTHER |
| | FACILITIES FOR THE STORAGE OF TOOLS AND MATERIALS |
| | HAVING COMBUSTIBLE CONSTRUCTION OR CONTENTS, SHALL BE |
| | IN ACCORDANCE WITH TABLE 4.2.1. |
| | |
| | 1) 20 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM |
| | ADJACENT STRUCTURES BY AT LEAST 30 FEET |
| | 2) 30 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM |
| | ADJACENT STRUCTURES BY AT LEAST 35 FEET |
| | 3) 40 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM |
| | ADJACENT STRUCTURES BY AT LEAST 40 FEET |
| | 4) 50 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM |
| | ADJACENT STRUCTURES BY AT LEAST 45 FEET |
| | 5) 60 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM |
| | ADJACENT STRUCTURES BY AT LEAST 50 FEET |
| | 6) GREATER THAN 60 FEET EXPOSED LENGTH SHALL BE |
| | SEPARATED FROM ADJACENT STRUCTURES BY AT LEAST 60 FEET |
| | **A 75 PERCENT REDUCTION IN SEPARATION DISTANCES SHALL |
| | BE PERMITTED TO BE APPLIED, PROVIDED AUTOMATIC |
| | SPRINKLER PROTECTION IS USED IN THE EXPOSING STRUCTURE. |
| | |
| | NOTES: |
| | (1) WHERE THE SEPARATION DISTANCE BETWEEN TEMPORARY |
| | STRUCTURES IS LESS THAN THE MINIMUM SEPARATION |
| | DISTANCE, THEN THE EXPOSING WALL LENGTH SHALL BE |
| | CONSIDERED TO BE THE SUM OF THE INDIVIDUAL EXPOSING |
| | WALL LENGTHS OF THE TEMPORARY STRUCTURES. |
| | (2) A 75 PERCENT REDUCTION IN SEPARATION DISTANCES |
| | SHALL BE PERMITTED TO BE APPLIED, PROVIDED AUTOMATIC |
| | SPRINKLER PROTECTION IS USED IN THE EXPOSING STRUCTURE. |
| | (3) THE SEPARATION DISTANCES APPLY TO SINGLE-LEVEL |
| | STRUCTURES ONLY. THIS TABLE DOES NOT APPLY TO |
| | MULTILEVEL, UNSPRINKLERED STRUCTURES. A LEVEL, WHERE |
| | APPLYING THIS TABLE, IS 3600 MM (144 IN.). |
| | |
| | 4.2.2* DETACHMENT BETWEEN TEMPORARY STRUCTURES, |
| | ADEQUATE TEMPORARY FIXED FIRE PROTECTION SYSTEMS, AND |
| | PORTABLE EQUIPMENT SHALL BE PROVIDED AS REQUIRED BY THE |
| | AUTHORITY HAVING JURISDICTION. |
| | |
| | PLEAE REIVEW AND PROVIDE FOR COMPLIANCE. |
| | |
| | FOR INFORMATIONAL PURPOSES, ABC DRYCHEM EXTINGUISHERS |
| | WILL BE ACCEPTED IN LIEU OF WET FIRE SPRINKLERS. |
| | |
| | |
| | 2) THERE IS NO FE LOCATED ON THE FLOOR PLAN. |
| | |
| | PER NFPA 101, CH 38 BUSINESS OCCUPANCY |
| | |
| | 38.3.5 EXTINGUISHMENT REQUIREMENTS. PORTABLE FIRE |
| | EXTINGUISHERS |
| | SHALL BE PROVIDED IN EVERY BUSINESS OCCUPANCY IN |
| | ACCORDANCE WITH SEC TION 9.9 |
| | |
| | 9.9* PORTABLE FIRE EXTINGUISHERS |
| | WHERE REQUIRED BY ANOTHER SECTION OF THIS CODE, |
| | PORTABLE FIRE EXTINGUISH ERS SHALL BE SELECTED, |
| | INSTALLED, INSPECTED, AND MAINTAINED IN ACCORDANCE |
| | WITH NFPA 10 |
| | |
| | A MINIMUM 2A10BC IS REQUIRED WITHIN OR DIRECTY OUTSIDE |
| | THIS TRAILER. |
| | |
| | PLEASE PROVIDE A NOTE OF ACKNOWLEDGMENT OF LOCATE A FE |
| | ON THE FLOOR PLAN. |
| | |
| | |
| | |
| | 3) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET |
| | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE |
| | ABOVE. |
| | |
| | |
| | 4) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE |
| | RE-SUBMITTAL OF THE ABOVE. |
| | |
| | |
| | PETER LEDUC |
| | FIRE MARSHAL |