2022-06-27 14:32:44THIS PLAN WAS REVIEWED AND FAILED BY CAITLIN L FRANCIS,
 FIRE INVESTIGATOR, WITH THE FOLLOWING COMMENTS:
  
 1) THE FIRE ALARM SYSTEM IS REQUIRED TO BE MONITORED
 ACCORDING TO NFPA 101
 31.3.4.1.1 APARTMENT BUILDINGS FOUR OR MORE STORIES IN
 HEIGHT OR WITH MORE THAN 11 DWELLING UNITS, OTHER THAN
 THOSE
 MEETING THE REQUIREMENTS
  
 2) ELEVATOR ROOMS ARE REQUIRED TO HAVE AUTOMATIC FIRE
 DETECTION IN ACCORDANCE WITH NFPA 72.
 21.3.11 ACTUATION FROM THE ELEVATOR HOISTWAY, ELEVATOR
 MACHINE
 ROOM, ELEVATOR MACHINERY SPACE, ELEVATOR CONTROL SPACE,
 OR ELEVATOR CONTROL ROOM SMOKE DETECTORS, OR OTHER
 AUTOMATIC
 FIRE DETECTION AS PERMITTED BY 21.3.9, SHALL CAUSE
 SEPARATE AND
 DISTINCT VISIBLE ANNUNCIATION AT THE BUILDING FIRE
 ALARM CONTROL
 UNIT, OR THE FIRE ALARM CONTROL UNIT DESCRIBED IN
 21.3.2, AND AT
 REQUIRED ANNUNCIATORS TO ALERT FIRE FIGHTERS AND OTHER
 EMERGENCY
 PERSONNEL THAT THE ELEVATORS ARE NO LONGER SAFE TO USE.
  
 3) PLEASE VERIFY YOU ARE MEETING THYE REQUIREMENTS FOR
 SLEEPING AREAS IN ACCORDANCE WITH NFPA 72
 18.4.5 SLEEPING AREA REQUIREMENTS
  
 4) INTERCONNECTED SINGLE STATION SMOKE ALARMS ARE
 REQUIRED TO BE INTERCONNECTED IN THE SLEEPING UNITS BUT
 NOT INCONJUCTION WITH THE FIRE ALARM PANEL. THIS IS
 ALSO NOT REQUIRED TO BE COVERED UNDER THIS PERMIT.
  