| Plan Review Notes For Permit 22061265 |
| Permit Number |
22061265 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2022-06-27 14:28:54 | THIS PLAN WAS REVIEWED AND FAILED BY CAITLIN L FRANCIS, | | | FIRE INVESTIGATOR, WITH THE FOLLOWING COMMENTS: | | | | | | 1) THE FIRE ALARM SYSTEM IS REQUIRED TO BE MONITORED | | | ACCORDING TO NFPA 101 | | | 31.3.4.1.1 APARTMENT BUILDINGS FOUR OR MORE STORIES IN | | | HEIGHT OR WITH MORE THAN 11 DWELLING UNITS, OTHER THAN | | | THOSE | | | MEETING THE REQUIREMENTS | | | | | | 2) ELEVATOR ROOMS ARE REQUIRED TO HAVE AUTOMATIC FIRE | | | DETECTION IN ACCORDANCE WITH NFPA 72. | | | 21.3.11 ACTUATION FROM THE ELEVATOR HOISTWAY, ELEVATOR | | | MACHINE | | | ROOM, ELEVATOR MACHINERY SPACE, ELEVATOR CONTROL SPACE, | | | OR ELEVATOR CONTROL ROOM SMOKE DETECTORS, OR OTHER | | | AUTOMATIC | | | FIRE DETECTION AS PERMITTED BY 21.3.9, SHALL CAUSE | | | SEPARATE AND | | | DISTINCT VISIBLE ANNUNCIATION AT THE BUILDING FIRE | | | ALARM CONTROL | | | UNIT, OR THE FIRE ALARM CONTROL UNIT DESCRIBED IN | | | 21.3.2, AND AT | | | REQUIRED ANNUNCIATORS TO ALERT FIRE FIGHTERS AND OTHER | | | EMERGENCY | | | PERSONNEL THAT THE ELEVATORS ARE NO LONGER SAFE TO USE. | | | | | | 3) PLEASE VERIFY YOU ARE MEETING THYE REQUIREMENTS FOR | | | SLEEPING AREAS IN ACCORDANCE WITH NFPA 72 | | | 18.4.5 SLEEPING AREA REQUIREMENTS | | | | | | 4) INTERCONNECTED SINGLE STATION SMOKE ALARMS ARE | | | REQUIRED TO BE INTERCONNECTED IN THE SLEEPING UNITS BUT | | | NOT INCONJUCTION WITH THE FIRE ALARM PANEL. THIS IS | | | ALSO NOT REQUIRED TO BE COVERED UNDER THIS PERMIT. | | | | | | CAITLIN L FRANCIS | | | FIRE INVESTIGATOR | | | WEST PALM BEACH FIRE RESCUE | | | 561-804-4728 | | | [email protected] |
|