| 2022-06-28 10:42:20 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE |
| | MARSHAL, WITH THE FOLLOWING COMMENTS: |
| | |
| | 1) THERE IS NO FLOOR PLAN SUBMITTED THAT INDICATES THE |
| | LOCATION OF THE BATHROOM NOR IF THEY ARE LOCATED ALONG |
| | A TENANT SEPARATION WALL REQUIRING MAINTENANCE/REPAIR |
| | OF THE FIRE RATED WALL SHOULD THE DEMO DAMAGE THAT |
| | WALL. |
| | |
| | PER NFPA 1 |
| | |
| | 1.7.12 PLANS AND SPECIFICATIONS. |
| | |
| | 1.7.12.1 THE AHJ SHALL HAVE THE AUTHORITY TO REQUIRE |
| | PLANS AND SPECIFICATIONS TO ENSURE COMPLIANCE WITH |
| | APPLICABLE CODES AND STANDARDS. |
| | |
| | FOR THE OFFICIAL RECORD, PLEASE PROVIDE A FLOOR PLAN |
| | INDICATING THE LOCATION OF THE BATHROOM(S) AND A NOTE |
| | OF ACKNOWLEDGEMENT TO MAINTAIN THE FIRE RATING OF THE |
| | BATHROOM WALL IF APPLICABLE. |
| | |
| | |
| | 1A) PLEASE INDICATE ON THE FLOOR PLAN THE LOCATION AND |
| | DIMENSION OF THE REMOVAL AND REPLACEMENT OF THE PRPOSED |
| | FLOORING. |
| | |
| | PER NFPA 1 |
| | |
| | 1.7.12 PLANS AND SPECIFICATIONS. |
| | |
| | 1.7.12.1 THE AHJ SHALL HAVE THE AUTHORITY TO REQUIRE |
| | PLANS AND SPECIFICATIONS TO ENSURE COMPLIANCE WITH |
| | APPLICABLE CODES AND STANDARDS. |
| | |
| | 1.7.12.6 PLANS SHALL BE SUBMITTED TO THE AHJ PRIOR TO |
| | THE ALTERATION OF THE MEANS OF EGRESS OR FIRE |
| | PROTECTION SYSTEMS OF ANY EXISTING BUILDING. |
| | |
| | PLEASE PROVIDE DETAILS. |
| | |
| | |
| | |
| | 2) THERE IS AN INDICATION WITHIN THE CONTRACT FOR THE |
| | INSTALLATION OF LAMINTATE OR VINYL FLOOR, BUT NO SPEC |
| | SHEET NOR PRODUCT NAME FOR THE ACTUAL PROPOSED |
| | FLOORING. |
| | |
| | LAMINATE OR VINYL FLOORING COULD HAVE DIFFERENT KINDS |
| | OF MANUFACTURING/TESTING FROM AROUND THE WORLD AND NOT |
| | ALL ARE TESTED AND MEETING LISTED AND NFPA STANDARDS. |
| | |
| | PER NFPA 101, CH 30 |
| | |
| | 30.3.3.3 INTERIOR FLOOR FINISH. |
| | 30.3.3.1 GENERAL. INTERIOR FINISH SHALL BE IN |
| | ACCORDANCE WITH |
| | SECTION 10.2. |
| | |
| | 10.2.7.2* FLOOR COVERINGS, OTHER THAN CARPET FOR WHICH |
| | 10.2.2.2 |
| | ESTABLISHES REQUIREMENTS FOR FIRE PERFORMANCE, SHALL |
| | HAVE A |
| | MINIMUM CRITICAL RADIANT FLUX OF 0.1 W/CM2. |
| | |
| | FOR THE OFFICIAL RECORD, PLEASE PROVIDE THE VINYL |
| | FLOORING NAME AND THE PRODUCT SPEC SHEETS OF THE |
| | PROPOSED FINISHED |
| | LAMINATE/VINYL FLOORING INDICATING THE FIRE BEHAVIOR |
| | RATING. |
| | |
| | |
| | |
| | 2) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET |
| | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE |
| | ABOVE. |
| | |
| | |
| | 3) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE |
| | RE-SUBMITTAL OF THE ABOVE. |
| | |
| | |