| 2023-07-21 09:50:56 | PETER E VALENTI |
| | BUILDING/MECHANICAL PLANS EXAMINER II/INSPECTOR |
| | [email protected] |
| | 561 805 6673 |
| | |
| | FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020) |
| | FBC B = FBC BUILDING |
| | FBC R = FBC RESIDENTIAL |
| | FBC EB = FBC EXISTING BUILDING |
| | FBC A = FBC ACCESSIBILITY |
| | FBC EC = FBC ENERGY CONSERVATION |
| | FBC M = FBC MECHANICAL |
| | FBC FG = FBC FUEL GAS |
| | |
| | 5TH MECHANICAL REVIEW DENIED: |
| | |
| | |
| | 1) PROVIDE HEAT LOAD CALCULATIONS FOR EACH UNIT FLORIDA |
| | ENERGY COCE 2020 |
| | |
| | 2) PROVIDE ENERGY CALCULATIONS FOR EACH UNIT C402.1 |
| | FLORIDA ENERGY CODE |
| | 2020 |
| | |
| | 4) THE PLAN SHEET M-1 NEEDS TO BE REVISED AS THE |
| | MINI-SPLIT LAYOUT IS NOT CLEAR: |
| | A.) THE LABELING OF EACH OF THE AIR HANDLINGS UNIT & |
| | CONDENSING UNITISS ARE THE SAME (AHU-1) & (CU-1). THESE |
| | NEED TO BE LOCATION SPECIFIC TO EACH AIR HANDLING UNIT |
| | AND EACH CONDENSING UNIT WITH THEIR OWN PLAN MARK. |
| | B.) THE TONNAGE INFORMATION FOR EACH CONDENSING UNIT AS |
| | INDICATED ON THE LAYOUT PLAN DOES NOT MATCH WITH THE |
| | INFORMATION ON THE SCHEDULE OF UNITS. |
| | C.) THE LINES ON THE LAYOUT SHEET THAT APPEAR TO |
| | REPRESENT REFRIGERANT AND CONDENSATE LINES NEED TO BE |
| | LABELED AND SOME OF THESE LINES ARE NOT CLEAR AS TO |
| | THEIR DESTINATIONS SUCH AS THE LINES FOR #1004 COVERED |
| | CONCRETE AREA. IT APPEARS THAT THE LINES FROM THE AHU |
| | LOCATED AT THE GAME ROOM CONNECTS WITHTHE 2-TON |
| | CONDENSING UNIT OUTSIDE OF #1004 BEDROOM #2 NOT THE |
| | CONDENSING UNIT NEAR THE GAME ROOM. |
| | D.) THE PLAN NEEDS TO SHOW THE LOCATION OF REFRIGERANT |
| | AND CONDENSATE LINES (ABOVE CEILING, WITHIN SOFFITS, |
| | BELOW SLAB ?) WITHIN THE INTERIOR OF STRUCTURES. |
| | |