| 2023-02-28 09:47:08 | ------IT DOES NOT APPEAR THAT THESE COMMENTS WERE |
| | ADDRESSED - PLEASE RESPOND ----- |
| | |
| | 4TH PLUMBING REVIEW |
| | |
| | V7 FPC - 2020 FLORIDA PLUMBING CODE |
| | V7 FGC - 2020 FLORIDA FUEL GAS |
| | V7 FRC - 2020 FLORIDA RESIDENTIAL BUILDING CODE |
| | V7 FAC - 2020 FLORIDA ACCESSIBILITY CODE |
| | V7 FEX - 2020 FLORIDA EXISTING BUILDING CODE |
| | V7 FEC - 2020 FLORIDA ENERGY CONSERVATION |
| | 2021 F.S. - 2021 FLORIDA STATUTES |
| | 2021 F.A.C. - 2021 FLORIDA ADMINISTRATIVE CODE |
| | 2017 WPB AMEND - 2017 WEST PALM BEACH AMENDMENTS TO THE |
| | FBC CHAPTER 1 |
| | |
| | THIS PLAN WAS REVIEWED FOR CODE COMPLIANCE AND FAILED |
| | BY RYAN BROWN WITH THE FOLLOWING COMMENTS. |
| | |
| | 1. COMMENT NOT ADDRESSED - SHOW A WATER HEATER DETAIL |
| | FOR THE COMMERCIAL SPACE(S) THAT INCLUDES THE MIXING |
| | VALVE AT THE WATER HEATER. |
| | 2020 FPC 607.1.1 - FOR THE COMMERCIAL SPACES, THERE |
| | SHALL BE A THERMOSTATIC MIXING VALVE (ASSE 1017) ON THE |
| | WATER HEATER TO REGULATE THE TEMPERATURE OF HOT WATER |
| | DELIVERY. |
| | |
| | 2. COMMENT NOT ADDRESSED - SHOW A LAVATORY DETAIL THAT |
| | INCLUDES A 1070 MIXING DEVICE REQUIRED FOR PUBLIC |
| | HANDWASHING STATIONS - 2020 FPC 607.1.2/419.5 - ON THE |
| | LAVATORIES THAT ARE ACCESSIBLE TO THE PUBLIC, THERE |
| | SHALL BE A MIXING VALVE COMPLIANT WITH ASSE 1070 TO |
| | REGULATE THE TEMPERATURE OF TEMPERED WATER. |
| | |
| | 3. COMMENT NOT ADDRESSED - SHOW A SHUT OFF VALVE THAT |
| | SERVES EACH INDIVIDUAL UNIT BEFORE IT ENTERS THE UNIT - |
| | 2020 FPC 606.1 - A FULL OPEN SHUT OFF VALVE SHALL BE ON |
| | THE WATER SUPPLY TO EACH UNIT. |
| | |
| | 4. COMMENT NOT ADDRESSED - |
| | 2017 WPB AMENDS 107.3.5.1.3 - THE REQUIRED RISER |
| | DIAGRAM IS NOT CODE COMPLIANT. |
| | A) CLOTHES WASHERS AND KITCHEN SINKS CANNOT BE INCLUDED |
| | IN WET VENTS OR OTHERWISE REQUIRED THEIR OWN INDIVIDUAL |
| | VENT. 2020 FPC 910.1 - 912.1 |
| | B) TWO SHOWER FIXTURE DRAINS ARE CONNECTED TO THE SEWER |
| | WITHOUT A VENT 2020 FPC 901.2.1 (SWR SHOULD BE SHWR FOR |
| | SHOWER) |
| | C) VENTS SHALL BE VERTICAL UNTIL THEY ARE AT LEAST 6" |
| | ABOVE THE FLOOD RIM OF THE FIXTURE SERVED. 2020 FPC |
| | 905.4 |
| | |
| | 5. COMMENT NOT ADDRESSED - |
| | 2020 FEX 906.1 - THE PUBLIC BATHROOM SHALL MEET THE |
| | FLORIDA ACCESSIBILITY CODE. |
| | A) 2020 FAC 604.3 - YOU'VE SHOWN AN ACCESSIBLE STALL |
| | DETAIL FOR A URINAL AND HAVE NOT PROVIDED A URINAL. |
| | SHOW A DETAIL THAT IS COMPLIANT FOR A WATER CLOSET. |
| | ADJUST THE SIZE OF THE BATHROOM TO MEET AN ACCESSIBLE |
| | WATER CLOSET. |
| | |
| | 6. COMMENT NOT ADDRESSED - |
| | 2020 FPC 403.1/403.3 - SHOW THE OCCUPANT LOAD OF THE |
| | RETAIL SPACES AND THE MINIMUM NUMBER OF FIXTURES |
| | REQUIRED FOR PUBLIC UTILIZATION FOR EACH SPACE OR |
| | ACCESS TO THE MINIMUM NUMBER OF FIXTURES REQIURED. A |
| | DRINKING FOUNTAIN AND/OR SERVICE SINK MAY BE REQUIRED. |
| | |
| | 7. COMMENT NOT ADDRESSED - |
| | 2017 WPB AMEND - 105.1/107.3 - IN CREATING A COMMERCIAL |
| | SPACE A BACKFLOW PERMIT IS REQUIRED. |
| | |
| | THE BUILDING SEWER CANNOT SERVE AS THE HORIZONTAL |
| | BUILDING DRAIN. SEVERAL FIXTURES APPEAR TO BE DIRECTLY |
| | CONNECTED TO THE SEWER WITHOUT VENT OR CLEANOUT. 2020 |
| | FPC 301.3 |
| | |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM. |
| | |
| | |