| 2023-06-06 16:18:53 | 4TH REVIEW |
| | DATE: TUES. JUNE 06TH/ 2023 |
| | ACTION: DENIED |
| | WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION |
| | SERVICES/ BUILDING DIVISION |
| | 2020 FBC- BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 22061262 |
| | ADD: 1911 N TAMARIND AVE |
| | CONT: BELACRIS CONSTRUCTION |
| | TEL: 305-244-0277 |
| | E-MAIL: [email protected] |
| | |
| | 2020 FLORIDA BUILDING CODE W 2020 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION |
| | |
| | 1-9) COMPLIED. |
| | 10A) COMPLIED. |
| | |
| | 10B) SEMI-COMPLIED. THE FLOOR PLAN SHOWS 3 EGRESSES TO |
| | THE COMMERCIAL AREA ACCESSIBLE BY THE PUBLIC. AT LEAST |
| | ONE ENTRANCE NEEDS TO BE AN ACCESSIBLE ENTRANCE LEVEL |
| | WITH THE EXTERIOR OF THE BUILDING. 2020 |
| | FBC-ACCESSIBILITY CODE SECTION 207.1 MEANS OF EGRESS |
| | SHALL COMPLY WITH SECTION 1003.2.13 OF THE |
| | INTERNATIONAL BUILDING CODE. MISSING SIGNAGE AT THE |
| | DOORS NOT ACCESSIBLE INDICATING WHERE THE ACCESSIBLE |
| | ENTRANCE IS LOCATED. |
| | |
| | |
| | 10C) COMPLIED. |
| | |
| | 10D) COMPLIED. |
| | |
| | 10E) COMPLIED. |
| | |
| | 10F) 4TH REVIEW. FORMER REVIEW SHOWED A WORK LIVE LOFT. |
| | THIS REVIEW THE FLOOR PLAN A-2.0 SHOWS A LOUNGE, OFFICE |
| | KITCHENETTE AND A ROOM NOT SHOWING A USE WITH WHAT |
| | APPEARS TO BE A PRIVATE BATH, SHOWER, WATER CLOSET AND |
| | LAV. PLEASE PROVIDE WHAT THE USEAGE OF THE ROOM IN |
| | FRONT OF THIS BATHROOM? BATHROOM MAYBE REQUIRED TO BE |
| | ACCESSIBLE. 2020 WEST PALM BEACH AMENDMENTS TO THE |
| | FLORIDA BUILDING CODE, CHAPTER 1, ADMINISTRATION |
| | 107.2.1. CONSTRUCTION DOCUMENTS SHALL BE SUFFICIENT |
| | CLARITY TO INDICATE THE LOCATION, NATURE AND EXTENT OF |
| | THE WORK PROPOSED AND SHOW IN DETAIL THAT IT WILL |
| | CONFORM TO THE PROVISIONS OF THIS CODE AND RELEVANT |
| | LAWS, ORDINANCES, RULES AND REGULATIONS, AS DETERMINED |
| | BY THE BUILDING OFFICIAL. |
| | |
| | 10G) 4TH REVIEW. A-2. THE COVERSHEET SITE PLAN LIST |
| | BOTH ADDRESSES AS INTERIOR REMODEL RESIDENCE VERSES |
| | SHEET A-2.0 COMMERCIAL RETAIL SPACE, DISCREPANCY IN |
| | PLANS. 2020 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE, CHAPTER 1, ADMINISTRATION 107.2.1. |
| | CONSTRUCTION DOCUMENTS SHALL BE SUFFICIENT CLARITY TO |
| | INDICATE THE LOCATION, NATURE AND EXTENT OF THE WORK |
| | PROPOSED AND SHOW IN DETAIL THAT IT WILL CONFORM TO THE |
| | PROVISIONS OF THIS CODE AND RELEVANT LAWS, ORDINANCES, |
| | RULES AND REGULATIONS, AS DETERMINED BY THE BUILDING |
| | OFFICIAL. |
| | |
| | 11) COMPLIED. |
| | |
| | |
| | 12) 4TH REVIEW. SHEET S1.0 IS USING ASCE 7-05 IN THE |
| | 2020 FBC-BUILDING WE ARE CURRENTLY USING THE ASCE 7-16. |
| | 3RD REQUEST SHEETS A-3.0 & A-4.0 BOTH SHOW EXTERIOR |
| | ELEVATIONS AND NEW EXTERIOR OPENINGS, WINDOWS AND |
| | DOORS. THERE IS NO WIND DESIGN CRITERIA. 2020 FBC-B |
| | 1603.1.4 WIND DESIGN CRITERIA. |
| | THE FOLLOWING INFORMATION RELATED TO WIND LOADS SHALL |
| | BE SHOWN, REGARDLESS OF WHETHER WIND LOADS GOVERN THE |
| | DESIGN OF THE LATERAL FORCE-RESISTING SYSTEM OF THE |
| | STRUCTURE: |
| | |
| | 12.1) 4TH REVIEW. THE WIND PEED IS NO LONGER 135MPH. |
| | 2020 FBC-BUILDING, VULT 170, VASD IS 132. |
| | .3RD REVIEW. ULTIMATE DESIGN WIND SPEED, VULT, |
| | (3-SECOND GUST), MILES PER HOUR AND NOMINAL DESIGN WIND |
| | SPEED, VASD, AS DETERMINED IN ACCORDANCE WITH SECTION |
| | 1609.3.1. |
| | |
| | 12.2. RISK CATEGORY. SHEET S1 THE RISK CATEGORY IS |
| | LISTED AS III, THIS IS FOR POLICE STATIONS, FIRE |
| | STATIONS & HOSPITALS. THIS BUILDING IS A RISK CATEGORY |
| | II. WITH LOWER ASSOCIATED PRESSURES. IMPORTANCE FACTOR |
| | IS NOT 1.15 THAT AGAIN IS FOR FOR POLICE STATIONS, FIRE |
| | STATIONS & HOSPITALS. THE IMPORTANCE FACTOR IS 1.0. |
| | |
| | 12.3. WIND EXPOSURE. APPLICABLE WIND DIRECTION IF MORE |
| | THAN ONE WIND EXPOSURE IS UTILIZED. TABLE 1609.7.2. |
| | HEIGHT AND EXPOSURE. ASCE 7-16 TABLE 30.3.1. |
| | |
| | 12.4. APPLICABLE INTERNAL PRESSURE COEFFICIENT. |
| | |
| | 12.5. DESIGN WIND PRESSURES TO BE USED FOR EXTERIOR |
| | COMPONENTS AND CLADDING MATERIALS SPECIFICALLY DESIGNED |
| | BY THE REGISTERED DESIGN PROFESSIONAL RESPONSIBLE FOR |
| | THE DESIGN OF THE STRUCTURE, PSF. |
| | |
| | 12.6.4TH REQUEST. PLEASE UPDATE PRESSURES FOR ZONES |
| | 1-5. TABLE 1609.7(2) ADJUSTMENT FACTORS FOR HEIGHT & |
| | EXPOSURE. PROVIDE THE MEAN ROOF HEIGHT FOR THE |
| | BUILDING. ASCE 7-10 TABLE 30.3.1. 1609.3.1 WIND SPEED |
| | CONVERSION VULT TO VASD. |
| | |
| | 13) . 4TH D REQUEST. PLEASE SUBMIT THE COMPONENTS AND |
| | CLADDING PRODUCT APPROVALS. 2020 FBC-B 1609.1.2 |
| | PROTECTION OF OPENINGS, 1609.6.4.4.1 COMPONENTS & |
| | CLADDING. FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS, |
| | ADMINISTRATIVE CODE 61G20-3.005, RULE 9N-3 NOV. 01/ |
| | 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION |
| | SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS: |
| | (31)(A) EXTERIOR DOORS |
| | (B) WINDOWS |
| | |
| | 14) 4TH REQUEST. W. P. B. 107.3.4. PRODUCT APPROVALS. |
| | THOSE PRODUCTS WHICH ARE REGULATED BY FLORIDA |
| | ADMINISTRATIVE CODE RULE 61G20 SHALL BE REVIEWED AND |
| | APPROVED IN WRITING (SHOP DRAWING STAMP OF APPROVAL) BY |
| | THE DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR |
| | JURISDICTIONAL APPROVAL. |
| | |
| | 15A) 4TH REQUEST. NOT ADDRESSED. SHEET A-3.0 ELEVATIONS |
| | SHOWS THE NORTH ELEVATION TO THE LEFT OF THE BUILDING |
| | PEOPLE ARE WALKING ON THE PUBLIC SIDEWALK ELEVATION 0 |
| | INCHES-0 FEET. THE NEW DOORS IN THE EXISTING OPENINGS |
| | SHOW A DOOR STOOP APPROXIMATELY 4 INCHES IN HEIGHT NONE |
| | OF THE DOORWAYS INTO ANY OF THE OFFICES OR LIVE/ WORK |
| | LOFT ARE ACCESSIBLE. GOOGLE MAPS SHOW THE DOORWAYS |
| | ELEVATED APPROXIMATELY 4 INCHES ABOVE THE SIDEWALK. |
| | 2020 FBC-ACCESSIBILITY CODE SECTION 207.1 MEANS OF |
| | EGRESS SHALL COMPLY WITH SECTION 1003.2.13 OF THE |
| | INTERNATIONAL BUILDING CODE (2000 EDITION AND 2001 |
| | SUPPLEMENT) OR SECTION 1007 OF THE INTERNATIONAL |
| | BUILDING CODE (2003 EDITION). 2020 FBC-ACCESS. CODE |
| | CHANGES IN LEVEL 303.2 AND 303.3. WHERE CHANGES IN |
| | LEVEL ARE PERMITTED IN THE FLOOR OR GROUND SURFACES, |
| | THEY SHALL COMPLY WITH SECTION 303. SEE 303.1 & 303.2. |
| | |
| | 15B) 4TH REVIEW. NO DOOR SCHEDULE. 2020 ACCESS. CODE |
| | 404.2.3. CLEAR WIDTH & SIZE OF DOORS, 2020 FBC-B |
| | 1010.1.1. WHERE THIS SECTION REQUIRES A MINIMUM CLEAR |
| | WIDTH OF 32- INCHES OR A 34-INCH DOOR MINIMUM. THE |
| | MINIMUM SIZE OF A SWING DOORS IS MEASURED CLEAR OPENING |
| | OF THE DOORWAY WITH THE SWINGING DOORS SHALL BE |
| | MEASURED BETWEEN THE FACE OF THE DOOR AND THE STOP, |
| | WITH THE DOOR OPEN 90 DEGREES. |
| | |
| | 15C) COMPLIED. |
| | |
| | 16) A TRANSMITTAL LETTER / NARRATIVE LISTING THE |
| | ORIGINAL REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF |
| | THE REVISION MADE, IDENTIFYING THE SHEET OR |
| | SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND WILL |
| | HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR |
| | ANTICIPATED COOPERATION. |
| | |
| | PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS |
| | REVIEW, SUBSEQUENT REMARKS MAYBE MADE IN THE NEXT |
| | REVIEW CYCLE. |
| | |
| | |
| | MY WORK HOURS ARE USUALLY TUES. & WED. 7:30 AM- 4:30 PM |
| | PART-TIME/ SEMI-RETIRED. |
| | |
| | IF YOU WISH TO SPEAK WITH A PLANS EXAMINER BEFORE I GET |
| | BACK INTO THE OFFICE CALL |
| | (561)805-6700 AND ASK FOR THE PLANS EXAMINER ON-CALL. |
| | THANK YOU. |
| | |