| 2022-09-02 06:20:19 | 1ST REVIEW FMC | | | PERMIT: 22061262 | | | | | | CODES IN EFFECT: 2020 | | | | | | FBC- FLORIDA BUILDING CODE | | | FMC- FLORIDA MECHANICAL CODE | | | FEC- FLORIDA ENERGY CONSERVATION | | | FGC- FLORIDA FUEL GAS | | | FEX- FLORIDA EXISTING BUILDING CODE | | | FRC- FLORIDA RESIDENTIAL BUILDING CODE | | | F.S.- FLORIDA STATUTES | | | FAC- FLORIDA ACCESSIBILITY CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) IS THIS A CHANGE OF USE FROM RESIDENTIAL R-3 TO | | | COMMERCIAL? IF SO PLEASE ADD CHANGE OF USE TO THE | | | APPLICATION. | | | | | | 2) PROVIDE ADDRESS OF THE PROJECT ON THE DRAWINGS. FBC | | | 107.3.5 | | | | | | 3) THE M.01 SHEET IS UNDER THE LIFE SAFETY DRAWING NAME | | | IN OUR SYSTEM AND THE LIFE SAFETY IS UNDER THE | | | MECHANICAL DRAWING NAME. PLEASE CORRECT. | | | | | | 4) PROVIDE THE ENERGY CALCULATIONS FOR THE NEW FINISHED | | | SQUARE FOOTAGE OF EXISTING GARAGE. FEC C402 | | | | | | 5) PROVIDE THE MECHANICAL EQUIPMENT SIZING CALCULATIONS | | | FOR EACH UNIT. FEC C403.2.1 | | | | | | 6) THE CENTER UNIT SHOWS A WASHER ON THE DRAWING, IS | | | THIS TO BE A STACKED WASHER/DRYER? IF SO, PROVIDE THE | | | DRYER DUCT INFORMATION ON THE DRAWING. FMC 504 | | | | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM. | | | | | | MICHAEL EDWARDS | | | MECHANICAL EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL. 33401 | | | 561-805-6728 | | | [email protected] | | | |
|