| 2022-07-01 11:26:15 | 1ST REVIEW FBC-2020 RES. PLUMBING |
| | PERMIT- 22060432 |
| | 6/22/2022 |
| | |
| | CODES IN EFFECT: |
| | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION |
| | 2020 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) SHEET 2: PROVIDE TDH CALCULATIONS- SECS. 4.4.9, |
| | 4.4.9.1 ANSI/APSP/ICC-7 & R4501.7.2 & R4501.7.3 FBC |
| | RES. |
| | |
| | 2) SHEET 2: PROVIDE THE PUMP CURVE ON THE SHEET MARKED |
| | UP TO SHOW THE TDH AND FLOW RATE OF THE SYSTEM- SECS. |
| | 4.4.9, 4.4.9.1 ANSI/APSP/ICC-7 & R4501.7.2 & R4501.7.3 |
| | FBC RES. |
| | |
| | 3) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE PUMP, |
| | FILTER, CHLORINATOR, HEATER, AND MAIN DRAIN ASSEMBLIES- |
| | SECS. R4501.6.2, R4501.6.6 FBC RES. |
| | |
| | 4) PLEASE NOTE THAT THE GAS HEATER SHALL BE INSTALLED |
| | UNDER A SEPARATE PERMIT- SECS. 105.1, 107.2.1, |
| | 107.3.5.3 WPB. |
| | |
| | 5) PLEASE NOTE AN RPZ BACKFLOW PREVENTER SHALL BE |
| | INSTALLED AT THE METER TO PROTECT THE POTABLE WATER |
| | SERVICE- SECS. C, D, & E WPB CROSS CONNECTION MANUAL. |
| | THE DEVICE SHALL BE INSTALLED UNDER A SEPARATE. A PVB |
| | BACKFLOW DEVICE IS ALSO REQUIRED FOR AUTOFILL |
| | INSTALLATIONS- SEC. P2908.3 FBC RES. |
| | |
| | 6) PROVIDE A PLUMBING SUB-PERMIT APPLICATION- SEC. |
| | 105.1 WPB. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |