2022-09-01 07:43:06****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
  
 FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
  
 COMMENTS NOT ADDRESSED. THE ONLY NEW DOCUMENT SUBMITTED
 WAS A SPEC SHEET FOR ADURA MAX. PLEASE SEE ITEM 3
 BELOW.
  
 1. PLANS WERE PREPARED BY AN ENGINEER BUT ARE NOT
 DIGITALLY SIGNED. UPLOAD DIGITALLY SIGNED PLANS. IF YOU
 WOULD LIKE FOR US TO CONFIRM BEFORE YOU UPLOAD THAT
 DOCUMENTS ARE DIGITALLY SIGNED, EMAIL TO [email protected]
 AND [email protected] FOR VERIFICATION.
  
 2ND REVIEW, RESPONSE LETTER STATES THAT THE ENGINEER
 WILL DEAL WITH THE BUILDING DEPARTMENT. THIS ENGINEER
 HAS A DIGITAL SIGNATURE. SOMEONE ON THE APPLICANT'S
 TEAM IS TO UPLOAD DIGITALLY SIGNED PAGES. THE NEW PAGES
 SHOULD BE NAMED SO THEY SUPERSEDE THE PAGES PREVIOUSLY
 UPLOADED.
  
 2. MANNINGTON ADURA MAX LVT FLOORING IS PROPOSED. SPEC
 SHEET INDICATES THAT THE SOUNDPROOFING IS ATTACHED, SO
 FLAME SPREAD IS NOT REQUIRED. THE STC AND IIC TESTS ARE
 REQUIRED.
  
 3. PROVIDE THE TEST REPORTS FOR THE FLOORING PROPOSED:
  
 PLEASE NOTE THAT TEST REPORTS ARE REQUIRED -
 MANUFACTURER SPEC SHEETS ARE NOT ACCEPTABLE DUE TO
 DISCREPANCIES BETWEEN SPEC SHEETS/BROCHURES AND TEST
 REPORTS FOR SOME MANUFACTURERS (NOT NECESSARILY THE
 MANUFACTURER SELECTED; THIS IS A GENERAL COMMENT)
  
 A. FBC 1207.2, FLOOR/CEILING ASSEMBLIES SEPARATING
 DWELLING UNITS FROM EACH OTHER OR FROM PUBLIC OR
 SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION CLASS
 (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) FOR AIR
 BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM E 90.
 THE TEST REPORT CANNOT INCLUDE A DROPPED GYPSUM
 CEILING. PROVIDE A COPY OF THE TEST REPORT.
  
 B. FBC 1207.3, FLOOR/CEILING ASSEMBLIES BETWEEN
 DWELLING UNITS OR BETWEEN A DWELLING UNIT AND A PUBLIC
 OR SERVICE AREA WITHIN THE STRUCTURE SHALL HAVE AN
 IMPACT INSULATION CLASS (IIC) RATING OF NOT LESS THAN
 50 (45 IF FIELD TESTED) WHEN TESTED IN ACCORDANCE WITH
 ASTM E 492. THE TEST REPORT CANNOT INCLUDE A DROPPED
 GYPSUM CEILING. PROVIDE A COPY OF THE TEST REPORT.
  
  