| 2022-08-15 07:57:05 | ****CORRECTIONS**** |
| | |
| | SAMANTHA HILL |
| | BUILDING PLANS EXAMINER |
| | [email protected] |
| | |
| | FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020) |
| | FBC B = FBC BUILDING |
| | FBC EB = FBC EXISTING BUILDING |
| | FBC A = FBC ACCESSIBILITY |
| | FBC EC = FBC ENERGY CONSERVATION |
| | |
| | COMMENTS NOT ADDRESSED: |
| | |
| | 1. PLANS WERE PREPARED BY AN ENGINEER BUT ARE NOT |
| | DIGITALLY SIGNED. UPLOAD DIGITALLY SIGNED PLANS. IF YOU |
| | WOULD LIKE FOR US TO CONFIRM BEFORE YOU UPLOAD THAT |
| | DOCUMENTS ARE DIGITALLY SIGNED, EMAIL TO [email protected] |
| | AND [email protected] FOR VERIFICATION. |
| | |
| | 2ND REVIEW, RESPONSE LETTER STATES THAT THE ENGINEER |
| | WILL DEAL WITH THE BUILDING DEPARTMENT. THIS ENGINEER |
| | HAS A DIGITAL SIGNATURE. SOMEONE ON THE APPLICANT'S |
| | TEAM IS TO UPLOAD DIGITALLY SIGNED PAGES. THE NEW PAGES |
| | SHOULD BE NAMED SO THEY SUPERSEDE THE PAGES PREVIOUSLY |
| | UPLOADED. |
| | |
| | 2. MANNINGTON ADURA MAX LVT FLOORING IS PROPOSED. SPEC |
| | SHEET INDICATES THAT THE SOUNDPROOFING IS ATTACHED, SO |
| | FLAME SPREAD IS NOT REQUIRED. THE STC AND IIC TESTS ARE |
| | REQUIRED. |
| | |
| | 3. PROVIDE THE TEST REPORTS FOR THE FLOORING PROPOSED: |
| | |
| | PLEASE NOTE THAT TEST REPORTS ARE REQUIRED - |
| | MANUFACTURER SPEC SHEETS ARE NOT ACCEPTABLE DUE TO |
| | DISCREPANCIES BETWEEN SPEC SHEETS/BROCHURES AND TEST |
| | REPORTS FOR SOME MANUFACTURERS (NOT NECESSARILY THE |
| | MANUFACTURER SELECTED; THIS IS A GENERAL COMMENT) |
| | |
| | A. FBC 1207.2, FLOOR/CEILING ASSEMBLIES SEPARATING |
| | DWELLING UNITS FROM EACH OTHER OR FROM PUBLIC OR |
| | SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION CLASS |
| | (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) FOR AIR |
| | BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM E 90. |
| | THE TEST REPORT CANNOT INCLUDE A DROPPED GYPSUM |
| | CEILING. PROVIDE A COPY OF THE TEST REPORT. |
| | |
| | B. FBC 1207.3, FLOOR/CEILING ASSEMBLIES BETWEEN |
| | DWELLING UNITS OR BETWEEN A DWELLING UNIT AND A PUBLIC |
| | OR SERVICE AREA WITHIN THE STRUCTURE SHALL HAVE AN |
| | IMPACT INSULATION CLASS (IIC) RATING OF NOT LESS THAN |
| | 50 (45 IF FIELD TESTED) WHEN TESTED IN ACCORDANCE WITH |
| | ASTM E 492. THE TEST REPORT CANNOT INCLUDE A DROPPED |
| | GYPSUM CEILING. PROVIDE A COPY OF THE TEST REPORT. |
| | |
| | |