Plan Review Notes
Plan Review Notes For Permit 22061151
Permit Number 22061151
Review Stop E
Sequence Number 1
Notes
Date Text
2022-08-04 10:00:43ELECTRIC REVIEW FAILED
 1) PLEASE DETAIL RECEPTACLE NEXT TO REFRIGERATOR
 COUNTERTOP AS REQUIRED PER NEC 210.52
 2) PLEASE DETAIL NOTES ON PLAN FOR ALL NEW ELECTRIC
 WORK TO COMPLY WITH THE FOLLOWING NEC REQUIREMENTS
 ENSURE ALL NEW WIRING COMPLIES WITH
 NEC 210.8 GFCI PROTECTION,
 NEC 210.12 AND NEC 406.4 ARC-FAULT PROTECTION,
 NEC 210.52 RECEPTACLE SPACING,
 NEC 406.12 AND NEC 406.4(D)(5) TAMPER RESISTANT
 RECEPTACLES,
 NEC 250.140 GROUNDING
 NEC 210.11 (C)(3) BATHROOM BRANCH CIRCUITS.
 AND SMOKE/CARBON ALARMS AS PER FBC R 314
 3) PROVIDE IDENTIFICATION AND SIGNATURE OF DESIGNER OF
 ALL DRAWINGS/PLANS SUBMITTED AS REQUIRED PER SECTION
 107.2.1 WPB, AND FLORIDA STATUTES 471.003(2)(H) &
 471.025.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM.
  
 CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2020 7TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2020 7TH ED.
 FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2020
 7TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020
 7TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION
 NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 V/R,
  
 MICHAEL PETERSON
 ELECTRICAL PLANS EXAMINER
 [email protected]
 561-805-6746
  
  